Abstract

In this study, the effects of the various conditions of frosting and defrosting on the behavior of defrosting in a fin-tube heat exchanger have been examined experimentally. The electric heater is used for defrosting in a fin-tube heat exchanger It is shown that there are several local maxima in the water draining rate. The amount of residual water on the heat exchanger after the completion of defrosting is kept constant due to surface tension on the heat exchanger. Without considering the degradation of the thermal performance due to the frosting, the defrosting efficiency is improved with increasing amount of the frost irrespective of the frosting condition. The defrosting behavior is affected by the frosting density as well as the frost accumulation, which vary with the experimental operating conditions during the frosting period. The heat loss to the surrounding air decreases, and the melting and defrosting efficiencies show high values with decreasing heat input.