Motion Characteristics of Particle in Model GIS

모의 GIS내 금속이물의 거동특성

  • 김경화 (홍성기능데 전기과) ;
  • 이재걸 (숭실대학교 공과대학 전기공학과) ;
  • 곽희로 (숭실대학교 대학원 전기공학과)
  • Published : 1999.11.01

Abstract

This paper describes the rmtion characteristics of a particle in GIS under AC voltage. To measure the motion characteristics of the particle, a model gas chamber and parallel plain electrodes were designed and manufactured lift-off voltages of wire and spherical particles on the electrode were calculated and rreasured, and electric charge was calculated. By using a high speed carrera, the rmtion characteristics of various particles with aw}ied voltages, such as motion pattern, lift-off time, lift-off height, were analyzed 1be lift-off voltages were greatly affected by diarreters of wire and spherical particles. At voltage around lift-off voltage, the stand-up particle in vertical state rmved up and down between electrodes and the height of the lift-off particle was low. At voltage around breakdown voltage, the particle repeated vertical rotation a few times while they were being lifted off, and then, they were floating between the electrodes.trodes.

본 논문에서는 교류전압 인가시 모의 GIS내에 존재하는 금속이물의 거동현상에 대해 연구하였다. 평행평판 전극을 내장한 가스챔버를 설계·제작하고, 전국내 선형 및 구형의 금속이물에 대해 부상전압을 계산 및 측정하였다. 또한 각각의 금속이물에 대전되는 전하량을 계산하였다. 고속카메라를 이용하여 금속이물의 종류 및 인가전압에 따른 거동양상과 부상시간, 부상높이 등의 거동특성을 분석하였다. 전계인가시 금속이물의 대전 전하량은 금속이물의 크기에 따라 증가하며, 부상전압은 서형 및 구형 금속이물의 직경에 큰 양형을 받는 것으로 나타났다. 금속이물의 부상이후 부상전압 부근의 전압에서의 선형 금속이물은 후 전극과 거의 수직인 상태로 상하 왕복운동을 하며, 거의 수직상태로 움직이는 거동 형태를 나타내었다. 절연파괴전압에 가까운 전압에서는 금속이물은 부상 중에 수회 수직회전을 반복하며, 장시간 부유하였다.

Keywords

References

  1. Fuji Denki Giho v.42 no.3 Characteristics of Sulfurhezafluoride and Some Considerations of Its Application Problems N. Izeki;S. Obara
  2. CICRE, Paris, Paper No. 23-07 Experiences and Considerations Regarding Erection Testing and Operation Availability of GIS in Sweden B. Wahlstrom, W. Lord;K. Petterson;R. Alvinson
  3. Denki Kyodo Kenkyu v.33 no.4 The Maintenance Standard of SF6 Gas Insulated Equipment Technical Committee on the Maintenance Standard of SF6 Gas Insulated Equipment
  4. IEEE Tans. Power Del. v.PWRD-2 Development of Compact 500kV 8000A Gas Insulated Transmission Line - Dirt Control during Field Jointing and Method for Detecting Conductive Particles K. Kaminage;M. Koshiishi;T. Hayashi, M.;Matsuki;T. Hara;N. Sugiyama
  5. 대한전기학회 추계학술대회 논문집 SF6가스내 금속이물의 전계에 의한 거동 및 미소방전 이재걸;곽희로(외 5인)
  6. 대한전기학회 추계학술대회 논문집 GIS 가스 챔버내에서 파티클 부상 특성 곽 희로;조 국희;권 동진
  7. CICRE, 15-09 Recent Research in the United States on the Effect of Particle Contamination Reducing the Breakdown Voltage in Compressed Gas-insulated Systems A.H. Cookson;P.C. Balin;H.C. Doepken
  8. Denki Kyodo Kenkyu v.33 no.4 The Maintenance Standard of SF6 Gas Insulated Equipment Technical Committee on the Maintenance Standard of SF6 Gas Insulated Equipment
  9. IEEE Tansactions on Power Delivery v.3 no.1 A Study on Effects of Conducting Particles in SF6 Gas and Test Methods for GIS T. Hattori
  10. IEEE Tansactions on Power Apparatus and Systems v.3;PAS-93 no.3 Particle-Initiated Breakdown between Coaxial Electrodes in Compressed SF6 Alan H. Cookson
  11. IEEE Tansactions on Power Apparatus and Systems v.PAS-100 no.9 SF6 Gas Insulated Analysis Technique and Its Application for Evaluation of Internal Conditions in SF6 Gas Equipment S. Tominaga;H. Kuwahara;K. Hirooka;T. Yoshioka