The heat transfer characteristics of a desorber for 150 RT absorption heat pump

150 RT급 흡수식 열펌프용 고온재생기의 열전달 특성

  • Published : 1999.05.01

Abstract

Experiments were carried out to study the heat transfer characteristics of a disrober for 150 RT LiBr-water absorption heat pump. An experimental apparatus was divided into four sections, a combustion chamber area, two bare-tube areas, and finally a finned-tube area to quantify the heat transfer rate of each section by measuring the generation rate of vapor. Dividing plates was installed at the upper inside part of deserter to prohibit the moving of vapor generated at heating tubes of a section to another section near. In the first bare-tube area, the generation rate of vapor was the largest among the four sections. The finned-tube area only contributed to give sensible heat increase of solution to the saturation temperature. The heat transfer area of the finned-tube area was 52.2%, which absorbed only 9.2% of the total heat from the combustion gas. On the contrary, the heat transfer area of the first bare-tube area was 16.6%, but it absorbed 52.4% of the total absorbed heat. The temperature of the solution at upper part at the finned-tube area was lower than that of the lower part, because weak solution came in upper part of the finned-tube area. But, this tendency was changed at the first and second bare-tube area due to the vigorous heat transfer and fluid flow enhanced by vapor generation through heating tubes. The overall heat transfer coefficient and heat flux were the largest at the first bare-tube area among the other sections.