Experimental study of performance characteristics of various fin types for fin-tube heat exchanger

휜-관 열교환기에 있어서 각종 휜 형상의 성능 특성에 관한 실험적 연구

  • 윤백 (삼성전자주식회사 냉공조사업부) ;
  • 김영생 (삼성전자주식회사 냉공조사업부) ;
  • 박환영 (삼성전자주식회사 냉공조사업부) ;
  • 박현연 (삼성전자주식회사 냉공조사업부)
  • Published : 1999.07.01

Abstract

Air side heat transfer and pressure drop for ø9.52 fin-tube heat exchanger with various types of slit and louver fins were measured, and compared with wave-slit fin. Longitudinal and transverse tube spacings of the heat exchangers are 21.65mm and 25mm respectively. Actual heat exchanger was tested using water, and the tests were performed for 2 row heat exchangers with 3 different fin spacings, 1.3, 1.5 and 1.7mm. The overall performance of the enhanced fins was evaluated by comparing heat transfer coefficient with respect to fan power.

Keywords