Performance Analysis of a Multi-type Inverter Heat Pump

멀티형 인버터 열펌프의 냉방성능해석에 관한 연구

  • Kim, Y. C. (Halla Climate Control Corp.) ;
  • Park, G. W. (Institute of Technology Shinsung ENG) ;
  • Youn, Y. (Digital Appliance Research Laboratory) ;
  • Min, M. K. (Department of Mechanical Engineering, Korea University) ;
  • Choi, Y, D, (Department of Mechanical Engineering, Korea University)
  • 김영철 (한라공조(주)) ;
  • 박근우 ((주)신성이엔지 기술연구소) ;
  • 윤영 (LG전자 디지털 어플라이언스 연구소) ;
  • 민만기 (고려대학교 기계공학과) ;
  • 최영돈 (고려대학교 기계공학과)
  • Published : 2001.03.01

Abstract

A system simulation program was developed for a multi-type inverter heat pump. Electronic expansion valve(EEV) was used to extend the capacity modulating range of the heat pump as expansion device. The program was also developed to calculate actual system performance with the building load variation with climate during a year. The performance variation of a multi-type hat pump with two EEV and an inverter compressor was simulated with compressor speed, capacity, and flow area of the EEV. As a result, the optimum operating frequency of the compressor and openings of the expansion device were decided at a given load. As compressor speed increased, he capacity of heat pump increased, the capacity of heat pump increased. Therefore flow area of EEV should be adjusted to have wide openness. Thus the coefficient of performance(COP) of the heat pump decreased due to increasement of compressor power input. The maximum COP point at a given load was decided according to the compressor speed. And under the given specific compressor speed and the load, the optimum openings point of EEV was also decided. Although the total load of indoor units was constant, the operating frequency increased as the fraction of load in a room increased. Finally ad the compressor power input increased, the coefficient of performance decreased.

Keywords

References

  1. ORNL/CON-80/R1 The Oak Ridge Heat Pump Models: 1 A Steady-state Computer Design Model for Air-to-Air Heat Pumps Ficsher,S.K.;Rice,C.K.
  2. Air Conditioning and Refrigeration Institue Unitary Air Conditioning Equipment ARI Standard 210/240
  3. Development of Simulation Program for Multi-Airconditioner B.D.Park;B.Y.Chung;D.Y.Ha;K.S.Im
  4. Ph.D.Thesis, Korea Univ.Mechanical eng Analysis and experiment on dynamic characteristics of an inverter heat pump Y.C.Park
  5. Ph.D.Thesis, Korea Univ.Mechanical eng A study on the transient characteristics of variable speed heat pump Y.J.Hwang