Abstract

In this paper, the distribution suspension porecelain insulators which had been used for long periods in the contaminated area were evaluated. The contaminated area is close to the sea and in the high density of industries. The heavily contaminated domestic and imported insulators were investigated by using electrical characteristics, such as power-frequency dry flashover voltage, power-frequency wet, flahover voltage, and leakage current. Also, these electrical results were compared with the contaminants on the surface. From these analysis, we found that the contamination from the industrial dust, only slightly decreased flashover voltage and increased leakage current. Therefore, the electrical properties of insulators used for 30 years in the area of coast and industrial complex were not much changed.

Keywords

References

  1. 송일근, 김찬영, 김주용, 한재홍, 이병성, '배전기자재의 수명예측 기준제정(최종보고서)', 전력연구원, pp. 7-75, 2000
  2. 김찬영, 김주용, 송일근, 이병성, '배전용 현수애자의 특성분석', 한국 전기전자재료학회 논문지, Vol. 13. No. 3. pp. 259-264, March 2000
  3. 송일근, 김찬영, '송전용 현수애자의 성능평가에 관한 연구', 대한전기학회 논문지,Vol. 49C, No. 7, pp. 406-411, July 2000
  4. E. A. Cherney, 'Cement Growth Failure of Porcelain Suspension Insulators', Transactions on Power Apparatus and Systems, Vol. PAS-102, No. 8. pp. 2765-2774, August 1983 https://doi.org/10.1109/TPAS.1983.317959
  5. R. Matsuoka, K. Kondo, K. Naito, M. Ishii, 'Influence of Nonsoluble contaminants on the flashover voltages of artificially contaminated insulators', IEEE Transactions on Power Delivery, Vol. 11, Issue 1, pp. 420-425, January 1996 https://doi.org/10.1109/61.484042
  6. K. Naito, 'A Comparative Study on Various Artificial Pollution Test Methods', NGK Review, No 30, pp. 29-37, 1966
  7. 장정태외, '전력설비의 염진해 대책에 관한 연구(III)', 한국전력공사 전력연구원, pp. 58-120, 1988