DOI QR코드

DOI QR Code

Optimal Flow Control of Ceiling Type Indoor Unit by PIV Measurements

PIV 유동 계측을 통한 천장형 실내기의 최적 제어 설계

  • 성재용 (순천대학교 기계자동차공학부) ;
  • 안광협 (LG 전자 디지털어플라이언스(연)) ;
  • 이기섭 (LG 전자 디지털어플라이언스(연)) ;
  • 최호선 (LG 전자 디지털어플라이언스(연)) ;
  • 이인섭 ((주)나노옵틱)
  • Published : 2003.08.01

Abstract

A heating flow discharged from a 4-way ceiling type indoor unit has been investigated to determine the design parameters for the optimal flow control. The flow was measured by a PIV(particle image velocimetry) system and an experimental model of 1/10 scale with a transparent room was devised by satisfying the Archimedes number. This similarity is generally used in cases where the forced convection has similar magnitude of the natural convection. To optimize the heating flow, several vane angles and vane control algorithms of cross and right angle controls were considered. Regarding the vane angle, experimental results show that 30$^{\circ}$is an optimal angle to avoid re-suction flows without significant increase in flow noise. Temperature distribution measured in the environmental chamber ensures the increased thermal comfort when compared to the case, 60$^{\circ}$angle. At the optimal angle, applying open/close control gives rise to more uniform distribution of the heating flow than without control. Especially, the cross-control seems to be satisfactory for thermal comfort.

Keywords

References

  1. Memarzadeh, F. and Manning, A., 2000, 'Thermal Comfort, Uniformity and Ventilation Effectiveness in Patient Rooms,' ASHRAE Annual Meeting, MN-00-11-3
  2. Kameel, R. and Khalil, E. E., 2001, 'Numerical Computation of the Fluid Flow and Heat Transfer in Air Conditioned Spaces,' Proc. ASME NHTC '01, NHTC2001-20084
  3. Takeshi, T. and Hikru, K., 1998, 'Flow in the Room Affected by the Supply Air from the Air-Conditioner,' VSJ, Vol. 18, No. 2, pp. 87-88
  4. An, K. H. and Lee, I. S., 2000, 'Temperature Field Measurement Around the Room Air Conditioner Using the LIF Technique,' 4th JSME-KSME Thermal Eng. Conference, Vol. 2, pp. 275-280
  5. An, K.-H. and Lee, I. S., 2000, 'Measurement and Control of the Thermal Fluid Flow Around the Room Air Conditioner,' Proc. National Congress on Fluids Engineering, pp. 407-410
  6. Koshima, M., 1996, 'Development of Energy Saving Room Air Conditioners,' Report of Mitsubishi Heavy Industry, Vol. 33, No. 2, pp. 78-81
  7. An, K.-H., Lee, I. S., Choi, H. S., Lee, G. S. and Huh, D., 2000, 'Visualization of the Air Conditioner Discharge Flow,' Proc. SAREK Winter Annual Conference, Vol. 2, pp. 613-617
  8. Park, S. K., Chee, S. K., Yang, G. and Oh, S. K., 2001, 'Effect of Discharge Angle on Indoor Thermal Comfort for a Cooling Air by 4-Way Ceiling Type Indoor Unit,' Proc. KSME Thermal and Fluid Eng. Conference, pp. 239-244