Comparison of Behaviors for Underground Flexible Pipes with Installation Gap

관로 이격거리에 따른 지중매설관의 거동특성 비교

  • Published : 2003.10.01

Abstract

Underground flexible pipes for electric cables are subject to external loads and surrounding soil pressure. Particularly, strain of flexible pipes is of great concern in terms of safety and maintenance of electric cables. In this paper, stress and strain of flexible pipes with two types of installation gap, ie, l0cm and naught, were compared to investigate the structural integrity of pipes from actual field test. The effect of degree of compaction and burial depth were also investigated to simulate the variety of construction situation. The results of the field test show that the strain criteria were satisfied under the burial depths of 80cm, 100cm and 120cm regardless of installation gap.

현행 지중전력선관로 건설시에 사용되는 표준공법은 관과 관사이의 거리를 l0cm 이격시켜 관로를 매설함에 따라 공정이 복잡하고, 경제적이지 못해 이에 대한 개선공법으로 관사이의 좌우이격거리를 없앤 접촉관 공법을 제안하였으며, 이 두 공법의 거동특성과 안정성을 비교$.$평가하고 지중매설관의 변형에 영향을 미치는 주요인자를 분석하기 위해 실규모 현장 실증실험을 수행하였다. 실험에 적용된 매설형태는 A-1급 도로포장아래 매설깊이 80cm, 100cm, 120cm 지점에 PE파형관이 각 공법형태에 맞게 매설되고, 외부하중으로 DB-24차량의 후륜하중 9.6ton이 매설관 상단 중앙에 정차했을 때 관이 받는 작용압력-변형률 특성을 분석하였다. 실험 결과, 지중매설관의 변형은 주로 시공과정중에 발생하는 것으로 나타났고, 특히, 모래되메움 공정 및 쇄석 포설 완료후에 변형이 가장 크게 발생하는 것으로 계측되었다. 그리고, 접촉관과 이격관 공법의 변형을 비교해 보면, 이격된 부분에 채워진 되메움재의 수동토압에 의한 저항압에 의존한 이격관 공법이 관과 관이 직접 접촉하여 관의 강성이 저항압으로 작용하는 접촉관 공법에 비해 변형이 작게 발생하는 것으로 분석되었다. 더불어 KS-C8455의 허용변형률 3.5%에 매설깊이 80cm, 100cm, 120cm에 묻힌 매설관이 공법 및 다짐방법에 관계없이 만족하는 변형률값을 보이고 있어 안전성을 확보하는 것으로 분석되었다.

Keywords

References

  1. 도로교 표준시방서 건교부
  2. 한국지반공학회 논문집 v.18 no.4 차량하증을 받는 지중연성관의 거동특성 이대수;김경열;상현규
  3. 관로 포설공법의 개선연구 이시용
  4. 지중관자재 적정규격 재정을 위한 기술 용역 이이환(외 13인)
  5. 지중배전 설계편람 조성수