TGA를 이용한 가교폴리에틸렌의 방사선 열화 평가

Evaluation of Radiation Degradation or Crosslinked Polyethylene using TGA

  • 이청 (충북대학교 전기공학과) ;
  • 김기엽 (한국원자력연구소 방사선응용연구팀) ;
  • 류부형 (동국대학교 안전공학과) ;
  • 임기조 (충북대학교 전기공학과)
  • Lee, Chung (Department of Electrical, Chungbuk National University) ;
  • Kim, Ki-Yup (Korea Atomic Energy Research Institute) ;
  • Ryu, Boo-Hyung (Department of Safety Engineering, Dongguk University) ;
  • Lim, Kee-Joe (Department of Electrical, Chungbuk National University)
  • 발행 : 2003.06.01

초록

Radiation degradation of crosslinked polyethylene(XLPE) was investigated using thermogravimetric analysis(TGA), The results of TGA were compared with FT-IR, melting temperature, oxidation induction time, and elongation at break on the XLPE exposed by $\gamma$-ray. 5% decomposition temperature of $\gamma$-ray irradiated XLPE showed similar tendencies with the case of elongation at break. Both properties agreed below 1000 KGy, however, did not show any remarkable characteristics above 1000 kGy, these properties can be useful to evaluate the radiation degradation of XLPE for only low irradiated region. Above 1000 kGy, the thermal decomposition activation energy showed decreased, on the contrary, increasing below 1000 kGy. Compared with FT-IR spectrum of irradiated XLPE, it was confirmed that the oxidation reaction was still occurring below 1000 kGy. Radiation degradation of XLPE was dependent upon the irradiation doses, TGA can be a useful tool to evaluate the degradation.

키워드

참고문헌

  1. K. Uchida and N. Shimizu, T. lEE Jpn., Vol. 112-A, No. 121, 1991
  2. S. S. Bamji, 'Threshold Voltage for Electrical Tree Inception in Underground HV Transmission Cables,' IEEE Trans. on EI., Vol. 27, No.2, pp. 402-404, 1992
  3. ANSI/IEEE Standard 383-1974, 'IEEE Standard for Typ Test of Class IE Electric Cable, Field Splices, and Connections for Nuclear Power Generating Station,' IEEE, 1974
  4. Annual book of ASTM standards, D 638, 'Standard Test Method for Tensile Properties of Plastics' Vol. 8.02, pp. 52-64, 1998
  5. Y. S. Cho et al, 'Thermal Degradation Kinetics of PE by the Kissinger Equation,' Material Chemistry and Physics, Vol. 52, pp. 94-97, 1998 https://doi.org/10.1016/S0254-0584(98)80013-8
  6. R. Setnescu et al, 'Chemiluminescence Study on the Oxidation of Several Polyolefins: I. Thermalinduced Degradation of Additives FreePolyolefins,' Polm. Degrd. Stabi., Vol. 60, pp. 377-383, 1998 https://doi.org/10.1016/S0141-3910(97)00096-7
  7. M. Al-Sheikhly and A. Christou, 'Tutorial How Radiation Affects Polymeric Materials,' IEEE Trans. on Reliability, Vol. 43, No.4, 1994
  8. K. Anandakumaran et al, 'Condition Assessment of Cable Insulation System in Operating Nuclear Power Plants,' IEEE Trans. on DEI., Vol. 6, No. 3, pp. 376-384, 1999 https://doi.org/10.1109/94.775626
  9. G. C. Montanari et al, 'Application of Oxidation Induction Time and Compensation Effect to the Diagnosis of HV Polymeric Cable,' IEEE Trans. on DEI., Vol. 3, No.3, pp. 351-360, 1996 https://doi.org/10.1109/94.506206
  10. R. M. Bell et al,'Correlation of Oxidation Induction Time with Thermal and Radiation Aging of EPR and XLPE Cable Insulation,' Conf. of ISEI., pp. 348-351, 1990
  11. F. J. Campbell, 'Radiation effects on the electrical properties of solid insulation in engineering,' ASTM Publication STP-783, Maryland, Vol. IIA, pp. 619-663, 1993
  12. B. Bartonicek et al, 'Lifeassessment Technique for Nuclear Power Plant Cables,' Radiat. Phys. Chem., Vol. 52, No.6, pp. 639-642, 1998 https://doi.org/10.1016/S0969-806X(98)00172-8
  13. 김기엽 외 3인,'아조화합물을 함유한 LDPE의 방사선 열화,' 한국산업안전학회 추계학술발표회 논문집, pp.301-306, 2000