A Numerical Study of a Room Fire for Fire Sizes II. wall fire and corner fire

FDS를 이용한 실내화재 모사의 문제점 II. 벽면형 및 모서리형 화재

  • Ko Kyung-Chan (Department of Safety Engineering, Graduate School, Pukyong National University) ;
  • Park Woe-Chul (Department of Safety Engineering, Pukyong National University)
  • 고경찬 (부경대학교 대학원 안전공학과) ;
  • 박외철 (부경대학교 안전공학과)
  • Published : 2004.09.01

Abstract

To confirm the previous finding that FDS predicts a fire growth rate too rapid compared with an experiment in a center fire in a room with an opening, the same computational fluid dynamics was applied to two types of fires, wall fire and comer fire. First the grid size was chosen to eliminate possible numerical errors due to a coarse grid system. Then the two types of fires were simulated for three different fire sizes, 7.65, 21.25, and 51.57kW for each type, which are the same as in the experiment to be compared with. The fires were predicted to grow too fist although the average temperatures and heights of the neutral planes were in good agreement with measurement.

Keywords

References

  1. S. H. Kim, H. S. Ryoll, "An experiment and numerical study on fire suppression using a water mist in an enclosur'", Building and Environment J., Vol. 38, pp. 1309-1316, 2003 https://doi.org/10.1016/S0360-1323(03)00134-3
  2. K B. McGrattan, H. R. Baurn, R. G. Rehm, A .Hamins, G. P. Forney, J. E. Floyd and S. Hostikka, Fire Dynamics Simulator Technical Reference Guide v.3, NIST, U.S.A., 2002
  3. 고경찬, 박외철, '화재크기에 따른 실내화재의 수치연구 - I. 중심형 화재', 산업안전학회지, 제19권, 제1호, pp. 18-22, 2003
  4. 정진용, 유홍선, 이재하, 홍기배,' 실내공간에서 화재 발생위치에 따른 연기거동에 대한 실험연구', 대한기계학회 논문집 B권, 제26권, 제5호,pp. 703-709, 2002
  5. 박준, 고경찬, 박외철,' 실내 프로판화재의 시뮬레이션', 한국산업안전학회 2004 춘계학술발표회 논문집, pp. 453-458, 2004