A New Anti-Islanding Method for Utility Interconnection of Distributed Power Generation System

분산전원시스템의 계통연계를 위한 새로운 단독운전 방지기법

  • 황인호 (충북과학대학 전기에너지시스템과)
  • Published : 2004.12.01

Abstract

This paper presents a new anti-islanding method for distributed power generation system (DPGS) using renewable energy. Based on the concept of real and reactive power mismatch, three different islanding conditions are analyzed. It is shown via analysis that islanding voltage is a function of real power alone, where as its frequency is a function of both real and reactive power. Using this analysis, a new anti-islanding method is developed. The proposed protection algorithm continuously perturbs ($\pm$5%) the reactive power supplied by DPGS while simultaneously monitoring the utility voltage and frequency. If a measurable frequency deviation took place by islanding, the real power of DPGS is further reduced to 80%. This detection method is shown to be fast acting under resonant loads. Possible islanding conditions are simulated and verified with analysis. Experimental results on a 0.5kW utility-interactive fuel cell system are suggested.

본 논문은 신$.$재생에너지를 이용한 분산전원시스템을 위한 새로운 단독운전 방지기법을 제시한다. 유효전력과 무효전력 불균형의 개념에 근거해서 3가지 다른 단독운전 조건이 분석된다. 단독운전 전압이 유효전력의 함수이고 그 주파수는 유효전력과 무효전력의 함수임이 분석을 통해 보여준다. 이 분석결과를 이용해서 새로운 단독운전 방지기법이 개발되었다. 제안된 보호 알고리즘은 분산전원에 의해 공급되는 무효전력을 계속적으로 $\pm$5% 변화시키면서 동시에 계통전압과 주파수를 관측한다. 만일 단독운전에 의해 측정할 정도의 주파수 이탈이 발생하면 더 나아가 분산전원의 유효전력을 80%로 감소시킨다. 이 검출기법은 공진부하에서도 빠르게 동작됨을 보여준다. 가능한 단독 운전조건이 모의되고 분석 증명된다. 0.5 kW 연계형 연료전지 시스템의 실험결과가 제시된다.

Keywords

References

  1. 황인호 외,'계통연계 태양광발전시스템의 제어기법 및 연계운전특성,' 전력전자학회 논문지,제5권 제2호,2000. pp.123-129
  2. John Stevens, Russel Bonn, Jerry Ginn, Sigifredo Gonzalez,Greg Kern, 'Development and Testing of an Approach to Anti- Islanding in Utility -Interconnected Photovoltaic Systems,' SAND 2000-1939, Unlimited Release, August 2000
  3. IEEE, Standard 929-2000, IEEE Recommended Practice for Utility Interface of Photovoltaic (PV) Systems
  4. IEEE P1547, Draft Standard for Interconnecting Distributed Resources with Electric Power Systems
  5. H. Kobayashi, K.Takigawa, E. Hashimoto, 'Method for Preventing Phenomenon of Utility Grid with a Number of Small Scale PV Systems,'in Proc. 22nd IEEE Photovoltaic Specialists Conf, 1991, pp.695-700
  6. A. Kitamura, M. Okamoto, F. Yamamoto, K. Nakaji, H. Matsuda, K. Hotta, 'Islanding Phenomenon Elimination Study at Rokko Test Center,' Proceedings of the 1st IEEE World Conference on Photovoltaic Energy COnversion (1994),pt. 1, pp. 759-762
  7. Gregory A. Kern, 'Sunsine3oo Utility Interactive AC Module Anti- slanding Test Results,' Proceedings of the 26th IEEE Photovoltaic Systems, 1997, pp.1265-1268
  8. G. A. Smith, P. A. Onions, D. G. Infield, 'Predicting Islanding Operation of Grid Connected PV Inverters,' lEE Proc. Electriml Power Applimtion, Vol. 14, No.1, January 2000, pp.1-6
  9. M. E. Ropp, M. Begovic, A. Rohatgi, 'Analysis and Performance Assessment ofthe Active Frequency Drift Method of Islanding Prevention,' IEEE Transactions on Energy Conversion, Vol. 14, No.3, September 1999, pp. 810-816 https://doi.org/10.1109/60.790956
  10. Yuyuma, S. Ichinose, T, Kimoto, K., Itami, T, Ambo,T, Okado, C., Nakajima, K., Hojo, S., Shinohara, S., Ioka, S., and Kuniyoshi, M, 'A high speed frequency shift method as a protection for islanding phenomena of utility interactive PV systems', Sol. Energy Mater. Sol Cells,1994, 35, (1-4), pp.477- 486
  11. M. E. Ropp, 'Design Issues for Grid-Connected Photovoltaic Systems,' Ph. D., Georgia Institute of Technology, Atlanta, GA, 1998
  12. Guo-Kiang Hung, Chih-Chang Chang, Chem-Lin Chen, 'Automatic Phase-Shift Method for Islanding Detection of Grid-Connected Photovoltaic Inverters,' IEEE Transaction on Energy Conversion, Vol.18, No.1, March 2003, pp.169-173