A Study on the Ventilation Effect by Various Location of Air Intake and Exhaust Fan of Bathroom in Apartment Housing

공동주택 화장실의 급기구 및 배기팬 설치위치에 따른 환기효과에 관한 연구

  • Published : 2004.10.01

Abstract

The mock-ups of ventilation system, which has been widely adopted for the bathroom with the area of 100 $m^2$ apartment housing, were established and tested to design mechanical ventilation for apartment housing bathroom where air supply exhaust are relatively important. These ventilation mock-ups were capable of controlling intake and exhaust, which has the size of supply openings as 40cm${\times}$1cm, 40cm${\times}$3cm, 40cm${\times}$5cm. They were established at five locations, spaced 40cm from each other at a height of 25cm from the floor. The exhaust fans were located at four corners and center of the ceiling. The results this ventilation effect measurement by different condition are showing that when the size of air supply is bigger and the location is lower, the effect of ventilation was relatively higher. In addition, as the distance between exhaust fan and air supply was farther, the ventilation effect were getting highly efficient.

Keywords

References

  1. 함진식(2001), 공동주택 화장실의 기계환기시스템에 관한연구, 한국주거학회지 제12권 3호. 141-148
  2. 함진식(1998), 급·배기 성능을 고려한 공동주택의 환기설계에 관한 연구, 대한건축학회 논문집 계획계 제4권 제11호 통권 제121호. 387-393
  3. 함진식(1999), 초고층 공동주택에서의 환기량 실측에 관한 연구, 대한건축학회 논문집 계획계 제15권 제3호 통권 제125호. 135-140
  4. 日本規格協會(1974)屋內換氣量測定方法(炭酸かス法)JIS A 1406
  5. 咸刻植(1988), トし-サ-ガス法による換氣量算定精度 に關する歌究 , 오사카대학 대학원 박사학위논문
  6. 함진식(1996), 건축공학을 위한 컴퓨터 프로그래밍, 보성각
  7. 함진식(1993), 트레이서 가스법에 의한 환기량 산정법의 정도에 관한 연구, 대한건축학회 논문집 9권 12호 통권 62호. 71-79
  8. 岸根卓郎(1974), 理論 應用統計學, 養賢堂