Technology of Waste Heat Recovery Using Heat Pipe Heat Exchanger for Industrial Practice

중고온 히트파이프를 이용한 열회수기술에 관한 연구

  • Lee Young-Soo (Unutilized Energy Research Center, Korea Institute of Energy Research (KIER)) ;
  • Kim Jong-Ryul (Unutilized Energy Research Center, Korea Institute of Energy Research (KIER)) ;
  • Chang Ki-Chang (Unutilized Energy Research Center, Korea Institute of Energy Research (KIER)) ;
  • Baik Young-Jin (Unutilized Energy Research Center, Korea Institute of Energy Research (KIER))
  • 이영수 (한국에너지기술연구원 미활용에너지연구센터) ;
  • 김종률 (한국에너지기술연구원 미활용에너지연구센터) ;
  • 장기창 (한국에너지기술연구원 미활용에너지연구센터) ;
  • 백영진 (한국에너지기술연구원 미활용에너지연구센터)
  • Published : 2004.11.01

Abstract

The present study has been conducted to develop a heat pipe heat exchanger for middle-high temperature ranged from 300 to $600^{\circ}C$. Heat transfer rate, overall heat transfer coefficient and temperature effectiveness were investigated using a heat pipe heat exchanger with Dowtherm A as working fluid. Theoretical analysis was also conducted, and the followings were obtained: (1) Heat exchange rate increased as waste gas temperature supplied to evaporator and frontal velocity in condenser increased, (2) Overall heat transfer coefficient increased by $3{\sim}7\%$ as frontal velocity in evaporator and condenser increased, (3) Temperature effectiveness was about $30\%$ in evaporator and was about $40\%$ in condenser, (4) Heat recovery rate was about $38\%$, (5) Pressure drop did not exceed $8\;mmH_{2}O$ under the running condition of $1{\sim}3Nm/s$, (6) Simulation results were corresponded with experimental results.

Keywords

References

  1. Lee, Y. S., 1992, For air-conditioning heat exchanger using heat pipe, Air-Conditioning and Refrigeration Engineering, SAREK, Vol.21, No.5, pp.423-438
  2. Lee, Y. S. and Jang, Y. S., 1990, A study on the characteristics of heat exchanger using heat pipe for various working condition, Journal of Air-Conditioning and Refrigeration Engineering, SAREK, Vol. 2, No.3, pp.155-165
  3. Perety, R. and Horbanic, B., 1984, Optimal heat pipe heat exchanger design, Journal of Heat Recovery System, Vol. 4, No.1, pp.924
  4. Azad, E. and Moztarzadeh, F., 1985, Design of air-to-water co-axial heat pipe heat exchanger,Journal of Heat Recovery System,Vol. 5, No.3, pp.217-224
  5. Japan Association of Heat Pipe, 1985, Practical Heat Pipe, p. 78
  6. Cho, M. J, Lee, K. W., Chang, K. C., Woo, J,S. and Ra, H. S., 1990, Development of the high efficiency heat exchanger using heat pipes, Report of KlER, pp. 56-62