A Study of the Application of Inert Gas Generator to the Fire Extinguishing System

불활성 가스 발생장치(Inert Gas Generator) 소화시스템 적용에 관한 연구

  • 한용식 (한국기계연구원 환경에너지기계연구본부) ;
  • 김명배 (한국기계연구원 환경에너지기계연구본부) ;
  • 김수용 (한국기계연구원 환경에너지기계연구본부)
  • Published : 2005.06.01

Abstract

A study of the utilization of inert gas generator(IGG) that generates a large amount of inert gas for the fire extinguishing equipment was performed. In this study, the fire extinction performance of gas generated from a 1GG which is implemented to a gas turbine was investigated. A simulated mixture gas of which composition is the same as that of the gas generated from ICG was used in all experiments. First, the extinction concentration was measured using a cup burner method. The extinction design concentration and the volume of extinction space was calculated by applying the obtained extinction concentration to a method recommended by NFPA 2001. In practical respects, the fire extinction performance of IGG-generated gas was confirmed through the fire suppression experiment within a $2m\times2m\times2m$ room.

대량의 비활성가스를 발생시키는 Inert Gas Generator(IGG)를 소화설비로 사용하기 위해 본 연구에서는 가스터빈을 채용한 IGG에서 발생되는 배기가스의 소화성능을 검토하였다. IGG에서 발생하는 가스는 조성을 동일하게 만든 모사 혼합가스를 이용하였으며, Cup Burner시험방법으로 소화농도를 측정하였다. 얻어진 소화농도를 NFPA 2001에서 권장하는 방법에 적용하여 소화설계 농도 및 소화공간 크기를 산정하였다. 또한, $2m\times2m\times2m$ 크기의 공간에서 화재진압 실험을 수행하여 실제 소화성능을 확인하였다.

Keywords

References

  1. NFPA 2001, Standard on Clean Agent Fire Extinguishing Systems(1996)
  2. ISO 6183, Fire Protection Equipment-Carbon Dioxide Extinguishing Systems for Use on Premises-Design and Installation, 1990(E)
  3. UL 1058, Haligenated Agent Extinguishing System Units(1995)
  4. 청정소화약제 INERGEN 소화설비, 한국화재소방학회(청정소화약제 및 시설기준)(1995)
  5. 김재덕, '가스계 소화시스템의 평가', 화재소방학회지, Vol. 1, No.1, pp.10-18(2000)
  6. FIS 002, 가스계 소화설비의 성능기준에 관한 인정기준, 한국소방검정공사(2000. 10. 9)