Analysis of the Harmonic Resonance in Primary Restorative Transmission Systems Using EMTDC

EMTDC를 이용한 시송전계통의 고조파공진 분석

  • Published : 2005.04.01

Abstract

Power system restoration following a massive or complete blackout starts with energizing of primary restorative transmission lines. During this primary restoration, inexpected overvoltage may happen due to nonlinear interaction between the unloaded transformer and the transmission system. This is known as the harmonic resonance phenomenon that may cause burning out of transformer or other devices. By now the harmonic resonance is reported in the extra high voltage system. This paper reports the detection of the resonance in Korean power system. Basic analysis and simulation of the harmonic overvoltage is presented using EMTDC.

Keywords

References

  1. M. Adibi, P. Clelland, L. Fink, H. Happ, R. Kafka, J. Raine, D. Scheurer, F. Trefny, 'Power System Restoration - A Task Force Report' IEEE Trans. on PWRS, Vol. 2, No. 2, pp. 271-277, May 1987
  2. M. M. Adibi et al., 'Power System Restoration Issues', IEEE Computer Applications in Power, Vol. 4, No. 2, pp. 19-24, April 1991 https://doi.org/10.1109/67.75871
  3. M. M. Adibi et al., 'Special Consideration in Power System Restoration The Second Working Group Report', IEEE Trans. on PWRS, Vol. 9, No. 1, pp. 15-21, February 1994 https://doi.org/10.1109/59.317562
  4. G. Morin, 'Service Restoration Following a Major Failure on the Hydro-Quebec Power System', IEEE Trans. on PWRD, Vol. 2, No. 2, pp. 454-462, April 1987
  5. M. M. Adibi, R. W. Alexander, 'Overvoltage Control During Restoration (Power System Restoration Working Group Report)', IEEE Trans. on PWRS, Vol. 7, No. 4, pp. 1464-1470, November 1992 https://doi.org/10.1109/59.207369