Development of Corona Cage Measurement System for Simulation on Electrical Environmental Characteristics of HVDC Overhead Transmission Line

HVDC 가공 송전선로 전기환경특성 모의시험용 코로나 케이지 계측시스템 개발

  • 길경석 (한국해양대학교 전기전자공학부) ;
  • 양광호 (한국전기연구원 전력연구단) ;
  • 이성두 (한전전력연구원 전력계통연구소) ;
  • 주문노 (한국전기연구원 전력연구단)
  • Published : 2006.05.01

Abstract

Corona characteristics of conductors are dependent on the electric field conditions in the immediate vicinity of the conductors. In case of DC transmission line, particularly, the space charge plays an important role in the electric field distribution. Therefore, DC corona cage simulation is necessary for long-term test in the same conditions. This paper presents the results of designing and constructing hardwares such as DC power supply, measurement system and DAS to carry out the simulation. The corona cage longitudinally is divided into five equal length sections and three inner sections of those are isolated from the ground of outer cage. The measurement items are radio noise, corona current, television noise, audible noise and meteorological conditions. In the next step, various simulations about the type and configuration of two or three candidate conductors will be conducted. And then finally an environmentally-friendly conductor for HVDC overhead transmission line will be decided.

Keywords

References

  1. 한국전력공사, 한국전기연구원, '초고압 직류 가공선로 설계 기술 및 핵심요소 기술 개발', pp. 39-40, 2004. 7
  2. IEEE Standard Procedures for the Measurement of Radio Noise from Overhead Power Lines and Substations, ANSI/IEEE Std 430-1986
  3. 주문노, 양광호, 명성호, 이동일, 신구용, '송전선로 EMI 특성실험용 인공잡음발생장치 설계.제작 및 적용', 대한전기학회 논문지, 51A-1-4, pp. 23-28, 2001. 12
  4. EPRI, 'HVDC Transmission LIne Reference Book', TR-102764. pp 2-18-3-26, 1993
  5. P. Sarma Maruvada, 'Corona Performance of High-Voltage Transmission Lines', Research Studies Press LTD, pp 120-135, 2000