Abstract

We simulated insulation defects of stator winding wire on high voltage generator by 5 types. 4 types have one discharge source and other one has multi discharge source by simulation. For accurate decision, measurements used to PRPD pattern to occurred partial discharge source of various types. In this research, when PRPD pattern carried out or analyzed pattern recognition of discharge source, it used to powerful tools. In this result, PRPD Pattern defined to have single discharge source of 4 types by insulation defect. When insulation defect simulated, all the defected winding have not the same result. Errors for a little different can make mistakes from a subtle distinction. The difference between internal and void discharge have magnitude of pulse amplitude of inner discharge bigger than void discharge and have a shape of bisymmetry. But void discharge has a shape of bisymmetry against maximum value on polarity respectively. In cases of slot and surface discharge, we confirmed to show similar results those other researchers. In case of multi-discharge, as a result of we could classify not perfect match with occurred patterns in single discharge eachother. In the future, we will have to recognize and classify with results of multi-discharge.

Keywords

References

  1. J. S. Johnson, 'Slot discharge detection between coils surfaces and core of high-voltage stator winding', Trans. Amer. Inst. Electr. Eng., Vol. 70, p. 1993, 1951 https://doi.org/10.1109/T-AIEE.1951.5060663
  2. J. E. Timperley, 'Incipient fault identification through neural RF monitoring of large rotating machine', IEEE Trans. Power. App. and Syst., Vol. 102, p. 693, 1983
  3. G. J. Paoletti and A. Golubev, 'Partial discharge theory and technologies realated to medium-voltage electrical equipment', IEEE Transaction on Industry Applications, Vol. 37, No.1, p. 90, 2001 https://doi.org/10.1109/28.903131
  4. G. C. Stone, 'Advancements during the past quarter century in on-line monitoring of motor and generator winding insulation', IEEE Trans. Dielectric. Insul., Vol. 9, p. 746, 2002 https://doi.org/10.1109/TDEI.2002.1038661
  5. C. Hudon and M. Belec, 'Partial discharge signal interpretation for generator diagonstics', IEEE Transaction on Dielectrics and Electrical Insulation, Vol. 12, No.2, p. 297, 2005 https://doi.org/10.1109/TDEI.2005.1430399