DOI QR코드

DOI QR Code

Compensation of Instantaneous Voltage Drop at AC Railroad System with Single-Phase Distributed STATCOM

전기철도 급전시스템의 순시전압강하 보상을 위한 단상 배전 STATCOM의 적용

  • Published : 2007.01.31

Abstract

An AC electrical railroad system has rapidly changing dynamic single-phase load, and at a feeding substation, three-phase electric power is transformed to the paired directional single-phase electric power. There is a great difference in electrical phenomenon between the load of AC electrical railroad system and that of general power system. Electric characteristics of AC electrical railroad's trainload are changed continuously according to the traction, operating characteristic, operating schedule, track slope, etc. Because of the long feeding distance of the dynamic trainload, power quality problems such as voltage drop, voltage imbalance and harmonic distortion my also occur to AC electrical railroad system. These problems affect not only power system stability, but also power quality deterioration in AC electrical railroad system. The dynamic simulation model of AC electrical railroad system presented by PSCAD/EMTDC is modeled in this paper, andthen, it is analyzed voltage drop for AC electrical railroad system both with single-phase distributed STATCOM(Static Synchronous Compensator) installed at SP(Sectioning Post) and without.

AC 전기철도 시스템은 동적 단상부하가 빠르게 변화하고, 전철 급전변전소에서 3상 전력을 단상 전력으로 변환한다. 이것은 일반 배전 시스템과 비교해서 AC 전기철도 시스템의 전기적인 현상들이 다르다는 것을 나타낸다. AC 전기철도 열차부하의 전기적인 특성은 동적부하의 운영과 운행 스케줄, 트랙의 구배 등에 따라 연속적인 변화를 받고 있다. 이와 같은 열차부하의 운영에 따른 급전거리가 길어 전압강하, 전압 불평형 및 고조파 왜곡현상 등의 전력 품질 저하요인이 발생하게 된다. 이러한 문제점은 상위계통인 송전시스템의 안정도에 악영향을 줄뿐만 아니라, 전기철도 급전시스템의 전력품질 저하, 전기철도차량의 통신장비, 운행 및 수송량 제한에도 영향을 미치게 된다. 따라서 본 논문에서는 전기철도시스템의 과도상태 평가를 위해 PSCAD/EMTDC를 이용한 평가모델을 제시하고, 전압 강하에 주안점을 두어, 전기철도 급전시스템의 말단 분기점(Sectioning Post)에 정지형 무효전력 보상장치인 단상 배전 STATCOM(Single-phase Static Synchronous Compensator)을 설치하여 그 작용에 따른 전압강하 보상을 평가하였다.

Keywords

References

  1. Keiji KAWAHARA, 'Compensation of Voltage Drop Using Static Var Compensator at Sectioning Post on AC Electric Railway System', PCC-Nagaoka'97, pp. 955-960, 1997
  2. P. C. Tan, 'Voltage Form Factor Control and Reactive Power Compensation in A 25[kV] Electrified Railway System Using A Shunt Active Filter Based On Voltage Detection', IEEE PEDS 2001-INDONESIA, p.605-610, 2001
  3. Zhu Yongqing, 'Balancing Compensation of Unbalanced Based on Single-Phase STATCOM', Tsinghua University Beijing
  4. Walmir Freitas, 'Impacts of AC Generators and DSTATCOM Devices on the Dynamic Performance of Distribution Systems', IEEE Transactions of power delivery, VOL. 20. pp. 1493-1501, 2005 https://doi.org/10.1109/TPWRD.2004.839181
  5. Mohan, 'Power Electronics', pp. 211-225
  6. Hun-soo Jung, 'Compensation of Voltage Drop Using the TSC-SVC in Electric Railway Power Supply System', Journal of KIIEE, VOL. 16, pp. 29-36, 2002
  7. Seung-Hyuk Lee, 'Compensate Voltage Drop for Autotransformer-Fed AC Electric Railroad System with Single-Phase STATCOM', Journal of the Korean Institute and Electrical Installation Engineers Vol. 16, No5, pp. 53-60, 2002 https://doi.org/10.5207/JIEIE.2002.16.5.053
  8. Joon-Ho Choi, 'A Study on the Application of UPQC in AC Railway System', Journal of KIIEE, VOL. 18, NO.6, pp. 220-229, 2004
  9. KOTRA, 'Kyung-bu Line Chochiyoun-Daeku Trasmission/Distribution Project Report', 2005
  10. Ko-rail, 'The Electric Locomotive', 2004

Cited by