DOI QR코드

DOI QR Code

Ground Surface Potential Distribution near Ground Rod Associated with Soil Structures

대지구조에 따른 접지봉 주번의 대지표면전위분포

  • 이복희 (인하대학교 전자전기공학부) ;
  • 정현욱 (삼성엔지니어링) ;
  • 백영환 (인하대 대학원 전기공학과)
  • Published : 2007.01.31

Abstract

This paper presents the distributions of ground surface potential rises as functions of soil structure and buried depth of ground rod. To propose fundamental data relevant to the reduction of electric shock of human beings due to ground surface rise, the ground surface potential rises near the ground rod were computed and measured. Ground surface potential rises near ground rod strongly depend on the soil structure, and an increase of the buried depth of ground rod results in a decrease of the ground surface potentials. The maximum ground surface potential appeared at the just above point of ground rod. Also, the measured results were in reasonably agreement with the data computered by grounding analysis program.

본 논문은 대지구조와 접지봉의 매설깊이에 따른 대지표면의 전위상승에 대해서 기술하였다. 대지표면의 전위상승에 따른 인체의 감전사고의 저감에 관한 기초적 자료를 제안하기 위해서 접지봉 부근에서의 대지표면전위를 계산하고 측정하였다. 접지봉 부근의 대지표면전위상승은 대지구조에 크게 의존하며, 매설깊이가 깊어질수록 낮아졌다. 대지표면전위상승은 접지봉의 직상부에서 최대이었으며, 측정결과는 접지해석프로그램으로 계산한 결과와 잘 일치하였다.

Keywords

References

  1. IEC 62305-1, Protection against lightning-, Part 3: Physical damage to structures and life hazard, p. 67, 2006.1
  2. 高橋建彦, '접지.등전위 본딩 설계의 실무지식', pp18-32, 2003
  3. B. H. Lee, J. S. Park and S. C. Lee, 'Experimental Investigations of Transient Impedances of Some Grounding Systems', 1997 Japan-Korea Joint Syms.ED & HVE, pp.237-240, 1997
  4. B. H. Lee, Su-bong. Lee,'Transient impedance of the Ground Grid and Deeply-driven Ground Rod', KIIEE Annual Spring Conference pp240-243, 2005
  5. 이복희, '접지의 핵심 기초기술', pp.52-55, 1999
  6. 이복희.정현욱, '접지봉 설치에 따른 전주 주변의 전위분포', pp 342-346, 2006 춘계학술대회 논문집