DOI QR코드

DOI QR Code

Partial Discharge Measurement by a Capacitive Voltage Probe in a Gas Insulated Switch

가스절연개폐기에서 용량성 전압프로브를 이용한 부분방전의 측정

  • 길경석 (한국해양대학교 전기전자공학과) ;
  • 박대원 (한국해양대학교 전기전자공학과) ;
  • 최수연 (한국해양대학교 전기전자공학과) ;
  • 김일권 (한국해양대학교 전기전자공학과) ;
  • 박찬용 (한국해양대학교 전기전자공학과)
  • Published : 2008.01.01

Abstract

An objective of this paper is to develop a partial discharge (PD) measurement device for monitoring gas insulated switches installed in power distribution system. A capacitive voltage probe was studied and designed to detect PD pulse without an electrical connection. The PD measurement device consists of the capacitive voltage probe attached outside of a bushing, a coupling network which attenuates AC voltage by 270 dB, and a low noise amplifier with the gain of 40 dB in ranges of 500 kHz${\sim}$20 MHz. The sensitivity of the prototype device calculated by a calibrator was 1.98 m V /pc. An application experiment was carried out in a 25.8 kV gas insulated switch and the peak pulse of 76.7 pC was detected. From the experimental results, it is expected that the PD measurement device can be applied to online monitoring system of gas insulated switches.

Keywords

References

  1. P. D. Agoris, S. Meijer, and J. J. Smit, 'E valuation of On-line Insulation Condition Assessment Techniques for power transformers', International Symposium on High-Voltage Engineering(ISH), Beijing, China, 2005
  2. 길경석, 박대원, 김일권, 최수연, 박찬용, '부분 방전에 의한 음향신호의 검출과 위치추정에 관 한 연구', 전기전자재료학회논문지, 20권, 10호, p. 907, 2007 https://doi.org/10.4313/JKEM.2007.20.10.907
  3. S. Tenbohlen, D. Uhde, J. Poittevin, H. Borsi, P. Werle, U. Sundermann, and H. Matthes, 'Enhanced Diagnosis of Power Transformers using On- and Off-line Methods: Results, Examples and Future Trends', CIGRE Paris, paper 12-204, 2000
  4. 황창호, 박신우, 김남열, 허창수, '평등전계에서 $SF_6/CF_4$ 혼합가스의 AC절연내력특성', 전기전자재료학회논문지, 20권, 4호, p. 381, 2007 https://doi.org/10.4313/JKEM.2007.20.4.381
  5. 권태호, 이종길, 이준호, '광섬유 센서를 이용한 절연유내의 부분방전 위치검출에 관한 연구', 전기전자재료학회논문지, 16권, 9호, p. 838, 2003
  6. 이복희, 길경석, 이형호, 정상진, 하성철, 김상 진, '가스절연 개폐설비에서 급준성 과도과전 압의 측 정장치', 대한전기학회논문지, 43권, 10 호, p. 1721, 1994
  7. F. H. Kreuger, 'Partial Discharge Detection in High-Voltage Equipment', Butterworth, p. 50, 1989
  8. IEC Publication 60270, High-voltage test techniques- Partial discharge measurement, 2000

Cited by

  1. A Study on the Acoustic Detection of Partial Discharges in Insulation Oil vol.23, pp.1, 2010, https://doi.org/10.4313/JKEM.2010.23.1.053
  2. A Study on PD Detection Methods for Cast-resin Dry-type Transformers vol.22, pp.9, 2009, https://doi.org/10.4313/JKEM.2009.22.9.786