Fire Test of Fiber Cocktail Reinforced High Strength Concrete Columns with Loading

섬유혼입공법을 적용한 고강도콘크리트 기둥의 재하 내화시험

  • 염광수 (GS건설(주) 기술연구소 연구개발팀) ;
  • 전현규 (GS건설(주) 기술연구소 연구개발팀) ;
  • 김흥열 (한국건설기술연구원 화재및설비연구센터)
  • Published : 2009.08.31

Abstract

The 180 minutes fire test based on the standard curve of ISO-834 were conducted on three RC column specimens with different constant axial loading ratios to evaluate the fire performance of fiber cocktail (polypropylene+steel fiber) reinforced high strength concrete column. The columns were tested under three loading levels as 40%, 50%, and 61% of the design load. No explosive spalling has been observed and the original color of specimen surface has been changed to light pinkish grey. The maximum axial displacements of three specimens were 1.5~2.2 mm. There was no reduction in load bearing capacity of each specimen exposed to fire and no effect were observed on the fire performance within 61% of the design load. The tendencies of the results with loading, such as the temperature distribution of in concrete and the changes in temperature rise due to the water vaporization in concrete, are very similar to those without loading. The final temperatures of steel rebar after 180 minutes of fire test resulted in 491.4${^{\circ}C}$ for corner rebar, 329.0${^{\circ}C}$ for center rebar, and 409.8${^{\circ}C}$ for total mean of steel rebar. The difference of mean temperature between corner and center rebar was 153.7${^{\circ}C}$ㅍ. The tendency of temperature rise in concrete and steel rebar changed after 30~50 minutes from the starting time of the fire test because the heat energy influx into corner rebar is larger than that into center rebar. The cause of decrease in temperature rise was due to the water vaporization in concrete, the lower temperature gradient of the concrete with steel and polypropylene fiber cocktails, the moisture movement toward steel rebars and the moisture clogging.

폴리프로필렌섬유와 강섬유를 혼입한 고강도콘크리트 기둥의 재하하중비에 따른 내화성능을 검증하기 위하 여 3기의 동일한 기둥시험체를 제작하여 각 시험체에 40%, 50%, 그리고 61%의 설계하중에 해당하는 고정압축하중을 재하한 후 ISO-834 표준내화곡선에 따라 180분간 내화시험을 실시하였다. 폭렬은 발생하지 않았으며, 표면부의 색은 분 홍색을 띤 회색으로 변했다. 시험체의 최대 연직방향 처짐은 1.5~2.2 mm로, 내화시험 중 화재로 인한 시험체의 강도손 실이 발생하지 않았으며, 설계하중의 61%이내에서 시험체의 내화성능은 영향을 받지 않았다. 깊이별 내부 콘크리트의 온도분포, 콘크리트 내부 수분 증발로 인한 온도상승이 변한 점 등 전반적으로 비재하 내화시험 결과와 매우 유사하였다. 180분 내화시험 후의 최종온도는 모서리철근이 491.4oC, 중앙철근이 329.0oC이며, 철근의 총 평균온도는 409.8oC이다. 전 반적인 온도분포의 경향은 비재하 내화시험과 매우 유사하였다. 모서리철근의 열에너지 유입량이 많기 때문에 중앙철 근과의 온도차(153.7oC)가 나타났으며, 가열 후 30~50분 사이에 온도상승추세가 변하였다. 이는 강섬유와 폴리프로필렌 섬유를 혼입한 콘크리트의 온도구배가 낮고, 철근으로의 수분이동과 내부 수분의 막힘현상, 그리고 수분의 기화열 때문이다.

Keywords

References

  1. Ali, F., “Is High Strength Concrete More Susceptible to Explosive Spalling than Normal Strength Concrete in Fire?,” Fire and Materials, Vol. 26, 2002, pp. 127-130 https://doi.org/10.1002/fam.791
  2. Nishida, A., Ymazaki, N., Inoue, H., Schneider, U., and Diederichs, U., “Study on the Properties of High-Strength Concrete with Short Polypropylene Fibre for Spalling Resistance,” Proceedings of International Conference on Concrete under Severe Conditions, CONSEC'95, Vol. 2, Sapporo, Japan, 1995, pp. 1141-50
  3. Atkinson, T., “Polypropylene Fibers Control Explosive Spalling in High-Performance Concrete,” Concrete, Vol. 38, No. 10, 2004, pp. 69-70
  4. Purkiss, J. A., “Steel Fibre Reinforced Concrete at Elevated Temperatures,” International Journal of Cement Composites and Lightweight Concrete, Vol. 6, No. 3, 1984, pp. 179-184 https://doi.org/10.1016/0262-5075(84)90006-X
  5. Lie, T. T. and Kodur, V. K. R., “Thermal and Mechanical Properties of Steel-Fibre-Reinforced Concrete at Elevated Temperatures,” Canadian Journal of Civil Engineering, Vol. 23, 1996, pp. 511-517 https://doi.org/10.1139/l96-055
  6. Suhaendi, S. L. and Horiguchi, T., “Effect of Short Fibers on Residual Permeability and Mechanical Properties of Hybrid Fibre Reinforced High Strength Concrete after Heat Eposition,” Cement and Concrete Research, Vol. 36, 2006, pp. 1672-1678 https://doi.org/10.1016/j.cemconres.2006.05.006
  7. 원종필, 장창일, 이상우, 김흥열, 김완영, “하이브리드 섬유보강 고강도콘크리트 기둥부재의 내화성능,” 콘크리트학회 논문집, 20권, 6호, 2008, pp. 827-832 https://doi.org/10.4334/JKCI.2008.20.6.827
  8. 김흥열, 채한식, 전현규, 염광수, “Fiber Cocktail을 혼입한 고강도콘크리트의 고온시 압축강도 특성 및 모델 제시에 관한 실험적 연구,” 한국콘크리트학회 학술발표논문집, 2007, pp. 605-608
  9. 염광수, 전현규, 김흥열, “섬유혼입공법을 적용한 고강도 콘크리트 기둥의 비재하 내화시험,” 콘크리트학회 논문집, 21권, 4호, 2009, pp. 465-471
  10. Ali, F., Nadjai, A., Silcock, G., and Abu-Tair, A., “Outcomes of a Major Research on Fire Resistance of Concrete Columns,” Fire Safety Journal, Vol. 39, 2004, pp. 433-445 https://doi.org/10.1016/j.firesaf.2004.02.004
  11. Kodur, A. K. R., Wang, T. C., and Cheng, F. P., “Predicting the Fire Resistance Behavior of High Strength Concrete Columns,” Cement & Concrete Composites, Vol. 26, 2004, pp. 141-153 https://doi.org/10.1016/S0958-9465(03)00089-1
  12. 한국산업규격, “건축 부재의 내화시험방법-일반요구사항 KS F 2257-1,” 한국표준협회, 2005, 9 pp.
  13. 한국산업규격, “건축 부재의 내화시험방법-기둥의 성능조건 KS F 2257-7,” 한국표준협회, 2006, 8 pp
  14. Personal Communication with 豊田 康二, 日本建築總合試驗所, 2007
  15. BSI, “Eurocode 2 Part 1.2 Design of concrete structures; General Rules-Structural Fire Design,” BSI, London, 2002, 102 pp
  16. “BS8110: Structural Concrete; Use of concrete,” UK, 1997.
  17. 국토해양부 고시, “고강도콘크리트 기둥·보의 내화성능 관리기준,” 제2008-334호, 2008, pp. 1-8
  18. 한국콘크리트학회, “콘크리트구조설계 기준,” 한국콘크리트학회, 2003, pp. 121-122
  19. 원종필, 장창일, 이상우, 김흥열, 김완영, “하이브리드 섬유보강 고강도콘크리트 기둥부재의 내화성능,” 콘크리트학회 논문집, 20권, 6호, 2008, pp. 827-832 https://doi.org/10.4334/JKCI.2008.20.6.827
  20. Chung, J. H. and Consolazio, G. R, “Numerical Modeling of Transport Phenomena in Reinforced Concrete Exposed to Elevated Temperatures,” Cement and Concrete Research, Vol. 35, 2005, pp. 597-608 https://doi.org/10.1016/j.cemconres.2004.05.037
  21. Concrete Center, Concrete and Fire, The Concrete Center, 2004, 4 pp

Cited by

  1. An experimental study on the residual mechanical properties of fiber reinforced concrete with high temperature and load vol.46, pp.4, 2013, https://doi.org/10.1617/s11527-012-9918-y
  2. Effect of aggregate on residual mechanical properties of heated ultra-high-strength concrete vol.49, pp.9, 2016, https://doi.org/10.1617/s11527-015-0758-4