DOI QR코드

DOI QR Code

Noise Evaluation Algorithm for Applying Complex Denoising Technique in On-line Partial Discharge Diagnosis System for Power Apparatus

전력기기의 운전중 부분방전 진단장치에서 복합잡음제거 적용을 위한 잡음평가 알고리즘

  • 이상화 (한국전기연구원 산업전기연구본부 전력기기연구센터) ;
  • 윤영우 (한국전기연구원 산업전기연구본부 전력기기연구센터) ;
  • 추영배 (거제대학 선박기술계열) ;
  • 강동식 (한국전기연구원 전력기기연구센터)
  • Published : 2009.02.28

Abstract

This paper introduces an evaluation code, which can numerically express the noise possessing degree of signals. By using this code, the best kind and setting of noise suppressing techniques can be chosen automatically. This code is applied to three kinds of specific denoising techniques; those are simple noise removing method in the count versus phase distribution, fuzzy logic method based on noise type in magnitude versus phase plot, and lastly, the technique using grouping characteristics of PD pulses in 3D plot of magnitude versus phase versus cycle. The algorithm shows good performance in the various real PD signals measured from various high voltage apparatuses in Korea.

최근 경제적 시간적 이유로 전력기기의 운전 중 부분방전 감시진단 장치가 많이 이용되는 추세에 있으나, 시 공간적으로 다양한 종류의 잡음의 영향이 문제시되고 있다. 이에 여러가지 잡음제거 기법들이 개발되었으나 범용적이지 않고 설정이나 환경에 따라 성능이 상이하다. 본 논문에서는 부분방전 측정신호의 잡음포함 정도를 수치적으로 제시할 수 있는 방법을 제시하였다. 이 기법이 적용되어 개발된 알고리즘을 이용하여, 다수 잡음제거 기법의 설정에 따른 다양한 결과 중 최선의 결과를 자동적으로 선택할 수 있었다. 운전 중 부분방전 감시진단 시스템에 사용되는 세 가지 잡음제거 기법에 적용하여 성공적으로 복합화 하였고, 국내 다양한 잡음 환경의 고전압 기기들로부터 실측한 데이터에 능동적으로 적응한 잡음제거 결과를 도출할 수 있었다.

Keywords

References

  1. IEEE Trial-Use Guide to the Measurement of Partial Discharges in Rotating Machinery, IEEE Std 1434-2000, 2000
  2. "Improved RF Monitoring," EPRI Project Record, RP232501, 1985
  3. S.R.Campbell, G.C.Stone, H.G.Sedding, K.S.Klempner, W.McDermid and R.G.Bussey, "Practical on-line partial discharge tests for turbine generators and motors" IEEE Trans. Energy Converstion, vol. 9, no.2, June 1994, pp. 281-287 https://doi.org/10.1109/60.300147
  4. K. Itoh, Y. Kaneda, A. Nishimura and T. Tanaka, "New Noise Rejection Techniques on Pulse-by-pulse Basis for On-line Partial Discharge Measurement of Turbine Generators," IEEETrans.EnergyConversion,vol.11, pp. 585-594, Sep. 1996 https://doi.org/10.1109/60.537029
  5. G.C.Stone and S.R.Campbell, "Digital Methods of eliminating noise in On-line Generator Partial Discharge Measurements," IEEE Winter Power Meeting, PanelSessionon Digital Techniques for Generator PDTexting, 1992
  6. P.Grunewald and J.R. Weidner, "On-line PD analysis in power plants – a successful tool for early fault detection," International Conference on Partial Discharge, Canterbury, September 1993, pp. 86-87
  7. S. Happe, H.-G. Kranz and W. Krause, "Real-time suppression of stochastic pulse shaped noise for on-site PD measurements", InternationalSymposiumon Nov. 2001 pp. 33-36
  8. T. Lin, R.K. Aggarwal, C.H. Kim, "Wavelet transform and artificial intelligence based condition monitoring for GIS", Sept.2003, Vol1, pp191–195 https://doi.org/10.1109/TDC.2003.1335207
  9. 강동식 외, "고압 회전기 On-line 부분방전 측정용 Ceramic Coupler 특성", 대한전기학회 논문지, Vol. 51C No.5, pp. 205-212, 2002