Effect on Flow Boiling Heat Transfer of Minichannel Diameter for R-410A

R-410A 비등열전달에 미치는 미세관경의 영향

  • Choi, Kwang-Il (Graduate School, Chonnam National University) ;
  • Pamitran, A.S. (Graduate School, Chonnam National University) ;
  • Oh, Jong-Taek (Department of Refrigeration and Air Conditioning Engineering, Chonnam National University) ;
  • Hrnjak, Pega (Department of Mechanical Science and Engineering, ACRC, University of Illinois at Urbana-Champaign) ;
  • Park, Chang-Yong (School of Mechanical Design and Automation Engineering, Seoul National University of Technology)
  • 최광일 (전남대학교대학원 냉동공조공학과) ;
  • ;
  • 오종택 (전남대학교 냉동공조공학과) ;
  • ;
  • 박창용 (서울산업대학교 기계설계.자동화공학부)
  • Published : 2009.12.10

Abstract

Two-phase flow boiling heat transfer of R-410A in horizontal small tubes was reported in the present experimental study. The local heat transfer coefficients were obtained over a heat flux range of 5 to 40 kW/$m^2$ a mass flux range of 170 to 600 kg/$m^2s$, a saturation temperature range of 3 to $10^{\circ}C$, and quality up to 1.0. The test section was made of stainless steel tubes with inner diameters of 0.5 and 3.0 mm, and lengths of 330 and 3000 mm, respectively. The test section was heated uniformly by applying a direct electric current to the tubes. The effects on heat transfer of mass flux, heat flux, inner tube diameter, and saturation temperature were presented. The experimental heat transfer coefficients are compared with six existing heat transfer coefficient correlations. A new boiling heat transfer coefficients correlation based on the superposition model for R-410A in small tubes was developed with mean deviation of 10.13%.

Keywords

References

  1. Kew, P. A. and Cornwell, K., 1997, Correlations for the prediction of boiling heat transfer in small-diameter channels, Applied Thermal Engineering, Vol. 17, No. 8-10, pp. 705-715 https://doi.org/10.1016/S1359-4311(96)00071-3
  2. Wambsganss, M. W., France, D. M., Jendrzejczyk, J. A. and Tran, T. N., 1993, Boiling heat transfer in a horizontal small-diameter tube, Journal of Heat Transfer, Vol. 115, pp. 963-975 https://doi.org/10.1115/1.2911393
  3. Bao, Z. Y., Fletcher, D. F. and Haynes, B. S., 2000, Flow boiling heat transfer of freon R11 and HCFC123 in narrow passages, Int J Heat and Mass Transfer, Vol. 43, pp. 3347-3358 https://doi.org/10.1016/S0017-9310(99)00379-8
  4. Choi, K. I., Pamitran, A. S., Oh, J. T. and Oh, C. Y., 2007, Boiling heat transfer of R-22, R-134a, and CO2 in horizontal smooth minichannels, Int J Refrigeration, Vol. 30, pp. 1336-1346 https://doi.org/10.1016/j.ijrefrig.2007.04.007
  5. Pettersen, J., 2004, Flow vaporization of CO2 in microchannels tubes, Experimental Thermal and Fluid Science, Vol. 28, pp. 111-121 https://doi.org/10.1016/S0894-1777(03)00029-3
  6. Lazarek, G. M. and Black, S. H., 1982, Evaporative heat transfer, pressure drop and critical heat flux in a small diameter vertical tube with R-113, Int J Heat Mass Transfer, Vol. 25, pp. 945-960 https://doi.org/10.1016/0017-9310(82)90070-9
  7. Tran, T. N., Wambsganss, M. W. and France, D. M., 1996, Small circular -and rectangularchannel boiling with two refrigerants, Int J Multiphase Flow, Vol. 22 No. 3, pp. 485-498 https://doi.org/10.1016/0301-9322(96)00002-X
  8. Kuo, C. S. and Wang, C. C., 1996, In-tube evaporation of HCFC-22 in a 9.52 mm microfin/smooth tube, Int J Heat Mass Transfer, Vol. 39, pp. 2559-2569 https://doi.org/10.1016/0017-9310(95)00326-6
  9. Yun, R., Kim, Y. and Kim, M. S., 2005, Convective boiling heat transfer characteristics of CO2 in microchannels, Int J Heat and Mass Transfer, Vol. 48, pp. 235-242 https://doi.org/10.1016/j.ijheatmasstransfer.2004.08.019
  10. Yan, Y. Y. and Lin, T. F., 1998, Evaporation heat transfer and pressure drop of refrigerant R-134a in a small pipe, Int J Heat and Mass Transfer, Vol. 41, pp. 4183-4194 https://doi.org/10.1016/S0017-9310(98)00127-6
  11. Gungor, K. E. and Winterton, H. S., 1987, Simplified general correlation for saturated flow boiling and comparisons of correlations with data, Chem Eng Res, Vol. 65, pp. 148-156
  12. Wattelet, J. P., Chato, J. C., Souza, A. L. and Christoffersen, B. R., 1994, Evaporative characteristics of R-12, R-134a, and a mixture at low mass fluxes, ASHRAE Trans, 94-2-1, pp. 603-615
  13. Jung, D. S., McLinden, M., Radermacher, R. and Didion, D., 1989, A study of flow boiling heat transfer with refrigerant mixtures, Int J Heat Mass Transfer, Vol. 32 No. 9, pp. 1751-1764 https://doi.org/10.1016/0017-9310(89)90057-4
  14. Shah, M. M., 1988, Chart correlation for saturated boiling heat transfer:equations and further study, ASHRAE Trans, 2673, pp. 185-196
  15. Chen, J. C., 1966, A correlation for boiling heat transfer to saturated fluids in convective flow, Industrial and Engineering Chemistry, Process Design and Development, Vol. 5, pp. 322-329 https://doi.org/10.1021/i260019a023
  16. Kandlikar, S. G., and M. E. Steinke, 2003, Predicting heat transfer during flow boiling in minichannels and microchannels, ASHRAE Trans, CH-03-13-1, pp. 667-676
  17. Zhang, W., Hibiki, T., and Mishima, K., 2004, Correlation for flow boiling heat transfer in mini-channels, Int J Heat and Mass Transfer, Vol. 47, pp. 5749-5763 https://doi.org/10.1016/j.ijheatmasstransfer.2004.07.034
  18. Chisholm, D., 1967, A theoretical basis for the Lockhart-Martinelli correlation for twophase flow, Int J Heat Mass Transfer, Vol. 10, pp. 1767-1778 https://doi.org/10.1016/0017-9310(67)90047-6
  19. Cooper, M. G., 1984, Heat flow rates in saturated nucleate pool boiling-a wide-ranging examination using reduced properties, In: Advances in Heat Transfer, Academic Press 16, pp. 157-239