Insulation Aging Characteristic Assessment on the Power cables with the Comparative Analysis Between Destructive and Nondestructive Diagnosis

파괴 및 비파괴진단 비교분석을 통한 케이블 열화특성평가

  • 이동영 (위덕대학교 에너지전기공학부)
  • Published : 2009.06.30

Abstract

The insulation aging characteristics and structural analysis test were performed to analyze the correlations among the insulation deterioration, diagnostic results and the breakdown strength for the underground power cables. From the results of the degree of crosslinking test, hot-oil test etc., it could be confirmed that there were no manufacturing defects in the power cables under test. From the results of the water tree test and chemical structural analysis, it could be confirmed that the aging status of cable under test were very poor, especially for B-Phase and the degree of aging was increased in the orders of A, C and B-phase. From the above results, it could be concluded that the insulation aging characteristic analysis results were well consistent with the diagnostic and breakdown test results, and also confirmed that the diagnostic system under consideration was successful to discriminate the bad cables which is likely to cause cable system failure.

본 논문에서는 지중전력케이블을 대상으로 케이블의 절연열화특성 분석시험을 통해 케이블의 절연열화와 절연 진단결과 및 파괴강도와의 상관관계에 대한 실증연구를 수행하였다. 시험대상 선로의 제조결함 여부를 확인하기 위해 가교도분석, 핫오일테스트 등을 실시한 결과 제조결함은 없는 것으로 확인되었다. 진단대상 선로는 3상 모두 장기간 사용에 의해 열화가 많이 진전되었고, 특히 B상이 수트리 길이 및 화학구조결함 농도 면에서 가장 열화된 케이블인 것으로 판단되며, C상, A상의 순으로 열화정도가 다소 감소함을 확인하였다. 상기 결과는 진단시험 및 파괴 강도시험 결과와 일치하며, 따라서 열화시정수법을 이용한 진단장치가 열화상태가 심각한 케이블의 선별에 효과적인 진단법임을 확인하였다.

Keywords

References

  1. D.Y. Yi, "Developement of Global Insulation Assessment System for Medium Votage Power Cable Systems", Journal of the Illuminating and Electrical Engineers, Vol. 17, No.2, pp.66-72, 2003
  2. IEEE P-400/D14-1999, "IEEE Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems."
  3. M. Beigert,"Destruction Free Ageing Diagnosis of Power Cable Insulation Using the Isothermal Relaxation Current Analysis", IEEE 1994 ISEI, Pittsburgh, June 1994
  4. S. Hvidsten, F. Faremo, J. Benjaminsen and E. Ildstads, "Condition Assessment of Water Treed Service Aged XLPE Cables by Dielectric Response Measurements", 21-201, Session 2000, CIGRE
  5. F.M. Rugg et al., "Infrared Spectrophotometric Syudies on Polyethylene. Ⅱ. Oxidation", J. Polym. Sci., pp.535-547, 1954 https://doi.org/10.1002/pol.1954.120137202
  6. EPRI Reports: EL-5387(RP 1782-1), EL-6207(RP 7897-2), EL-7076( RP 7897-1)