A Field Application Case of Direct Ice Slurry Transporting System for District Cooling

지역냉방용 직접순환식 아이스슬러리 시스템의 현장적용 사례

  • Yoo, Ho-Seon (Department of Mechanical Engineering, Soongsil University) ;
  • Lee, Sang-Hoon (Department of Mechanical Engineering, Soongsil University) ;
  • Lee, Yoon-Pyo (Korea Institute of Science and Technology)
  • Published : 2009.09.10

Abstract

In order to investigate the feasibility of a direct ice slurry transporting system for the purpose of district cooling, a case study of field application is performed. The research aims include the field measurement of ice packing factor, the performance of coldness delivery, and the branching characteristics of ice slurry. Two representative types of pipe branch are dealt with in this work. For the slurry flow with ice volume fraction of 0.16 or less, the pipe blocking due to aggregation is not observed. Based on the time-wise variation of temperature in the storage tank, a calculating method of ice packing factor is newly developed, which seems to be useful when the brine concentration is unknown. It is confirmed that the mass flow rate of ice slurry per unit cooling load is markedly reduced with increasing the ice content. The pumping power also decreases, but remains unchanged for high ice fractions. The distribution of ice particle before and after branching shows a good uniformity within the range of 5% difference, but yields a unique trend depending on the flow rate.

Keywords

References

  1. Lee, D. W., 2001, Ice slurry type storage system and utilization, The magazine of the SAREK, Vol. 30, No. 6, pp. 21-26
  2. Lee, D. W., 2001, Cold heat transportation using ice slurry, The magazine of the SAREK, Vol. 30, No. 12, pp. 8-14
  3. Lee, D. W., 2003, Cold heat transportation using ice slurry and Its utilization, HARFKO symposium, pp. 286-298
  4. SAREK, 2005, Feasibility study on the ice slurry-based district cooling system, Final Report submitted to Korea District Heating Corporation
  5. Jung, H. W., Peck, J. H., Park, S. S., Kim, Y., Kang, C., and Hong H., 2007, A real time measurement of ice concentration of ice slurry in pipe, Korean Journal of Air Conditioning and Refrigeration Engineering, Vol. 19, No. 8, pp. 599-606
  6. Melinder, Å., 2006, Updating and Extending secondary fluid data for various refrigeration and heat pump applications, 7th IIR Gustav Lorentzen Conference on Natural Working Fluids, Trondheim
  7. Kwon, J. S., Lee, Y. P., Lee, S. H., Yoo, H., and Yoon, S. M., 2008, Continuous Ice Slurry Production and Control of Ice Packing Factor in a Pipe for the District Cooling, Korean Journal of Air Conditioning and Refrigeration Engineering, Vol. 20, No. 12, pp. 825-832
  8. Lee, Y. P., Shin, H. T., 1997, Use of Ice slurry for district cooling, Proceeding of the SAREK 1997 Summer Annual Conference, pp. 827-841