Adjustment of Valve Opening in Ondol Hot Water Distributor

온돌 난방분배기의 개도조정

  • Received : 2010.03.20
  • Published : 2010.07.10

Abstract

In housing units constructed recently in Korea, the length of ondol coil is different in each room, so the flow rate of hot water is adjusted by setting valve opening. If the flow rate is not appropriate for heating load, the room temperature seriously deviates from the set temperature range for comfort. In particular, too small valve opening can induce a noise by cavitation. In order to adjust the valve opening, two methods by zone area and a new method by return temperature rise were modelled and simulated using TRNSYS and EES. As a result, heating energy consumption during one week was the same on three methods, but the room temperature of the new method minimally deviated from the range of set temperature with a low possibility of noise.

Keywords

References

  1. Lee, K. N., Ryu, S. R., Kim, Y. Y., Yeo, M. S., and Kim, K. W., 2004, A study on the energy simulation considering the response time of radiant floor heating system, Proceeding of the SAREK 2004 Summer Conf., pp. 620-625.
  2. Choi, J. M., Lee, K. N., Ryu, S. R., Yeo, M. S., and Kim, K. W., 2005, A study for flow-rate balancing when the system resistance changes in the control of the radiant floor heating system, Proceeding of the SAREK 2005 Winter Conf., pp. 129-134.
  3. Choi, J. M., Lee, K. N., Ryu, S. R., Kim, Y. Y., Yeo, M. S., and Kim, K. W., 2007, A study on the required supply water temperature calculating method for the control of multizone radiant floor heating system, Korean J. of Air Conditioning and Refrigeration Engineering, Vol. 19, No. 1, pp. 77-85.
  4. Hong, H., Kim, S., and Yoo, H., 2009, An energy saving using ondol heating schedule control of housing units, Proceeding of the SAREK 2009 Winter Conf., pp. 139-144.
  5. Hong, H. and Kim, S., 2009, Method of dynamic simulation for ondol heating, Proceeding of the SAREK 2009 Winter Conf., pp. 145-150.
  6. Samyang Valve, 2003, Design for Ondol Hot water Heating and Header.
  7. Solar Energy Lab., 2005, TRNSYS 16.1 reference manual, University of Wisconsin-Madison.