An Analytical Study on the Prediction of Indoor Air Quality and the Reduction of Air Conditioning Load in Bio Safety Level 3 Laboratory

생물안전 3등급시설의 공기환경 예측 및 공조부하 절감에 대한 해석

  • Hong, Jin Kwan (Department of Building Equipment and System Eng., Gachon University) ;
  • Park, Hyun Jin (Korea Institute of Patent Information)
  • 홍진관 (가천대학교 건축설비학과) ;
  • 박현진 (한국특허정보연구원)
  • Received : 2012.08.16
  • Published : 2012.11.10

Abstract

In this study, the multizone simulation for biosafety of BSL3 lab. and energy simulation are carried out simultaneously by using linked model of CONTAM and TRNSYS. In BSL3 lab., annual energy consumption is approximately five to ten times more than the magnitude of the office building. This is because required air change rate is extremely large and it is difficult to maintain room pressure difference efficiently. To maintain pressure difference between laboratory rooms through sealing condition of doors and proper airflow control is significant. In this study, to predict indoor environment of the BSL3 lab.(Influenza A research lab.), the multizone simulation for four kinds of biohazard scenario is also performed as part of risk assessment. Multizone and energy simulation results by using linked model show that these approaches are used as a tool for the energy efficient design and operation method for the safer BSL3 lab. facilities.

Keywords

References

  1. Laboratories fot the 21st Centry, An Introduction to Low-Energy Design, U. S. Environmental Protection Agency Office of Administration and Resources Management, 2000.
  2. Hong, J. K., 2010, A Case Study on the Validation of BSL3 Laboratory and Engineering Cost Evaluation of BSL3 Laboratory, Design, Construction and Validation Workshop of BS L3 Laboratory, pp. 229-253.
  3. National Technical Information Service U. S. Department of Commerce Springfield, VA, Vol. 22161.
  4. TRNSYS, 1994, Solar Energy Lab. Rep., University of Wisconsin-Madison.
  5. McDowell, T. P., Thornton, J. W., Emmerich, S., and Walton, G., 2003, Integraton of airflow and energy simulation using CONTAM and TRANSYS, ASHRAE transaction, Vol. 109, No. 2, kc-03-10-2.
  6. Hong, J. K. and Choi, S. G., 2007, The Study on the Disinfection performance of Indoor Microorganism using Energy Consumption Analysis through the Linked Model of CONTAM and TRANSYS, International Conference on Sustainable Building Asia, pp. 855-860.
  7. Park, H. J. and Hong, J. K., 2010, A Study on the Prediction of Indoor Environment in Bio Safety Level 3 Laboratory according to Biohazard Scenario, Journal of SAREK, Vol. 22, No. 11, pp. 745-750.
  8. NIH, Biosafety in Microbiological and Biomedical Laboratories, 4th Edition, 1999.
  9. Walton, G. N., 2005, CONTAM 2.4 User Guide and Program Documentation, NISTIR, Vol. 7251.
  10. ASHRAE Standard 52.2-1999, Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size, American Society of Heating, Refrigerating and Air-Conditioning Engineers, 2000.