DOI QR코드

DOI QR Code

An Analysis on Thermal Performance and Economic of Heat Recovery Ventilation System Integrated with Window

창호통합형 배열회수 환기시스템의 열성능 및 경제성 평가

  • Sung, Uk-Joo (Department of Architectural Engineering, Graduate School of Hanyang University) ;
  • Cho, Soo (Korea Institute of Energy Research) ;
  • Song, Kyoo-Dong (Department of Architectural Engineering, Hanyang University)
  • 성욱주 (한양대학교 대학원 건축공학과) ;
  • 조수 (한국에너지기술연구원) ;
  • 송규동 (한양대학교 건축공학부)
  • Received : 2012.05.22
  • Published : 2012.08.10

Abstract

This study is intended to analyze the thermal performance and evaluate the applicability about non-duct type heat recovery ventilation system integrated with window. Eventually, economic analysis of the system is conducted according to building energy saving ratio of it. As results of the thermal performance, the U-factor of the window conducted on the basis of KS F 2278 appears to $1.8W/m^2K$, and the effective heat exchange efficiency of the ventilator conducted on the basis of KS B 6879 appears 49.95% for cooling, 66.89% for heating. In the applicability evaluated by TRNSYS 16, the caes of applying the heat recovery ventilator integrated with window is found to reduce the cooling or heating load by 2.9% or 13.5% than the non-ventilator case. The results of economic analysis taking a side of consumer is verified as the payback is 3 years, and the accumulated earning is 1,408,133 won in terms of '600,000 won/unit' for initial cost, 10 years for useful life of the system.

Keywords

References

  1. Kim, K. H. and Yee, J. J., 2008, A study on operating method by energy evaluation and performance evaluation of heat recovery ventilator according to outdoor conditions, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 20, No. 1, pp. 57-64.
  2. Chung, M. H. and Yoo, S. Y., 2005, A study on the factors affecting the performance of total heat exchanger for exhaust heat recovery, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 17, No. 10, pp. 956-964.
  3. Kim, S. S., Yee J. J., and Lee, Y. G., 2008, Performance evaluation of energy recovery ventilator with various outdoor climate conditions, Journal of Architectural Institute of Korea, Vol. 24, No. 8, pp. 261-268.
  4. Chang, H. J. and Hong, S. J., 2008, A study on the performance of heat recovery ventilators for apartment houses, Korean Journal of Air- Conditioning and Refrigeration Engineering, Vol. 20, No. 1, pp. 26-34.
  5. Kim, N. H., Cho, J. P., Song, G. S., and Kim, D. H., 2008, Performance of a plate-type enthalpy exchanger mode of papers having different properties, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 20, No. 8, pp. 547-555.
  6. Lim, T. K., Jeon, B. H., Kim, J. W., Jung, S. H., Lee, S. K., and Ahn, Y. C., 2012, A study on the performance of heat recovery ventilator according to the properties of spacer, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 24, No. 3, pp. 224-229. https://doi.org/10.6110/KJACR.2012.24.3.224
  7. Chung, M. H. and Oh, B. K., An experimental study on performance of paper heat exchangers for exhaust heat recovery ventilation system, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 24, No. 3, pp. 240-246. https://doi.org/10.6110/KJACR.2012.24.3.240
  8. Chang H. J., 2006, Long term energy simulation of ventilation system for apartment houses, Proceedings of the SAREK Winter Annual Conference, pp. 114-119.
  9. Lee, S. R., Jeung, N. G., Lee, K. K., Lee, S. H., and Oh, M. D., 2010, Life cycle cost analysis of energy saving performance for apartment, Proceedings of the SAREK Winter Annual Conference, pp. 254-259.

Cited by

  1. Numerical Analysis on the Coupled Operation of Ventilation Window System and Central Cooling System vol.31, pp.4, 2015, https://doi.org/10.5572/KOSAE.2015.31.4.385
  2. Economical evaluation of damaged vacuum insulation panels in buildings vol.103, pp.1757-899X, 2015, https://doi.org/10.1088/1757-899X/103/1/012014