Analysis of Cooling Energy Saving by Variable Air Volume System and Cold Aisle Containment System in Internet Data Center

가변풍량제어시스템과 냉복도밀폐시스템의 적용에 의한 데이터센터의 냉방에너지 절감 효과 분석

  • Park, Byung-Yoon (Department of Architecture, Suwon Science College) ;
  • Jung, Yong-Ho (Department of Building Equipment and Fire Protection System, Chungwoon University)
  • 박병윤 (수원과학대학교 건축과) ;
  • 정용호 (청운대학교 건축설비소방학과)
  • Received : 2013.07.30
  • Accepted : 2013.09.04
  • Published : 2013.09.30

Abstract

In order to keep the data center server room temperature condition, cooling energy consumption has been rapidly increased as the increasing internal heat gain from the server devices. And the cooling units for server systems are fully operated to satisfy the indoor temperature condition, it results in the excessive energy consumption. There are many wastes of cooling energy which is caused by the structural problems in data center server room. For example, a leakage by the electric cable hole, mixing or recirculation of hot air from the hot aisle to the cold aisle, short circulation of the CRAC(Computer Room Air Conditioning), and others. So there are many strategies to reduce the waste of cooling energy in data center. In this study, cold aisle containment system and variable air volume system were proposed among the various strategies to reduce the energy cosumption. To verify the effectiveness of the energy saving system, test bed which is same with exist server room was set up in IDC(Internet Data Center) building and comparative experiments were carried out in actual conditions. As the result, in case of setting server room temperature $30^{\circ}C$, the server device inlet temperature exceeded $27^{\circ}C$ class 1 condition of the ASHRAE standard. But in case of setting server room temperature below $26^{\circ}C$, the range of inlet temperature of server system was $18{\sim}26^{\circ}C$ by cold aisle containment system. In case of variable air volume system and setting server room temperature $26^{\circ}C$, total energy saving was 19.8% to conventional cooling system. After all, variable air volume system and cold aisle containment system were proved to be the effective solution for energy saving cooling system.

Keywords

Acknowledgement

Supported by : 국토해양부