An experimental study on the fireproof performance of fire damper in accordance with insulation conditions on the coaming and blade

코밍 방열 두께 및 블레이드 방열 유무에 따른 방화 댐퍼의 내화성능에 관한 실험적 연구

  • 최태진 (한국조선해양기자재연구원 안전환경팀) ;
  • 김정식 (한국조선해양기자재연구원 안전환경팀) ;
  • 최경관 ((주)동아풍력 기술연구소) ;
  • 임영수 (한국조선해양기자재연구원 안전환경팀) ;
  • 김유택 (한국해양대학교 해사대학 기관시스템공학부)
  • Received : 2013.04.05
  • Accepted : 2013.05.15
  • Published : 2013.05.31

Abstract

In this paper, Fire resistance test was carried out to obtain class H-120 thermal insulation of fire dampers according to a hydrocarbon fire conditions. Specimens were fabricated three different types according to the change of the insulation system applied to damper blade and coaming which were measured surface temperature by performing the fire resistance test. As a test result, specimen-1, 2 of an uninsulated damper blade were exceeded thermal insulation acceptance criteria at 21 minutes, 46 minutes respectively, but specimen-3 of an insulated damper blade was satisfied thermal insulation acceptance criteria during 120 minutes. The test results showed that the insulation of the damper blade is an important factor in the fireproof performance of fire dampers concerning the coaming length minimum 500 mm on the unexposed side as specified test standard.

본 논문에서는 방화 댐퍼의 H-120 등급 방열성능 확보를 위하여 탄화수소화재 조건에 따른 내화 실험을 수행하였다. 실험체는 댐퍼 블레이드 방열 유무와 코밍 방열재 두께의 변화에 따라 3가지 타입으로 제작 하였으며, 내화실험을 통한 비 노출면 단열재와 코밍 표면 온도를 측정 하였다. 내화실험 결과 댐퍼 블레이드를 방열하지 않은 실험체-1, 2는 각각 21분, 46분경과 방열성능 허용 기준을 초과하였으며, 댐퍼 블레이드를 방열한 실험체-3은 120분 방열성능을 만족하는 것으로 나타났다. 방화 댐퍼 내화 시험 기준에 따른 비 노출면 최소 돌출길이(500 mm) 조건에서 댐퍼 블레이드 방열조건이 방화 댐퍼 내화성능에 큰 영향을 미치는 요인임을 확인할 수 있었다.

Keywords

References

  1. J.-S. Kim "Offshore standard for fire & explosion protection materials," Journal of the Korean Society of Marine Engineering, vol. 36, no. 6, pp. 751-752, 2012 (in Korean)
  2. T.-J. Choi, U.-T. Kim, and J.-S. Kim, K.-K, S.-C. Jang, and S.-M. Han, "An experimental study on the hydrocarbon fire resistance test of the "H" class divisions," Proceedings of the 36th KOSME Spring Conference, p. 205, 2012 (in Korean).
  3. BS, "Fire tests on building materials and structures. method for determination of the fire resistance of elements of construction (general principles)," UK, BS 476 Part 20, 1987.
  4. DNV, "Standard for certification-no. 2.9," NOR, Type Approval Programme No. 470, 2003.
  5. ASTM, "Standard test methods for determining effects of large hydrocarbon pool fires on insulated marine bulkheads and decks, constructed of steel," USA, ASTM F 2133-01, 2007.
  6. IMO, "Adoption of the international code for application fire test procedures," IMO Res. 307(88), 2010.
  7. ISO, "Fire-resistance tests - elements of building construction - part 3," ISO 834-3, 2012.
  8. Cerak Wool New-Bio 1100-1300, www.kccworld.co.kr/eng/business/insulation_materials, Accessed December 11, 2012.

Cited by

  1. An experimental study on the fireproof performance of fire damper according to change of the insulation conditions on the exposed side and unexposed side of the coaming vol.38, pp.1, 2014, https://doi.org/10.5916/jkosme.2014.38.1.99
  2. 해양플랜트용 H-120 Class 파이어 댐퍼의 성능 실험 vol.13, pp.2, 2013, https://doi.org/10.14775/ksmpe.2014.13.2.131
  3. A60급 구획 적용 격벽 관통용 관의 열전달 특성 II: 관 재질 및 단열재 종류에 따른 방화시험 vol.33, pp.4, 2019, https://doi.org/10.26748/ksoe.2019.027
  4. Meta-Models and Genetic Algorithm Application to Approximate Optimization with Discrete Variables for Fire Resistance Design of A60 Class Bulkhead Penetration Piece vol.11, pp.7, 2013, https://doi.org/10.3390/app11072972
  5. Evaluation on Sensitivity and Approximate Modeling of Fire-Resistance Performance for A60 Class Deck Penetration Piece Using Heat-Transfer Analysis and Fire Test vol.35, pp.2, 2013, https://doi.org/10.26748/ksoe.2021.012
  6. A60급 갑판 관통 관의 방화성능 평가를 위한 과도 열전달 해석과 화재시험 vol.22, pp.4, 2021, https://doi.org/10.5762/kais.2021.22.4.1
  7. 다중 섬 유전자 알고리즘 기반 A60 급 격벽 관통 관의 방화설계에 대한 이산변수 근사최적화 vol.20, pp.6, 2021, https://doi.org/10.14775/ksmpe.2021.20.06.033