DOI QR코드

DOI QR Code

Performance Analysis of a Wet Air-Cycle Refrigeration System

습공기사이클 냉동시스템의 성능해석

  • Won, Sung Pil (School of Mechanical Engineering, University of Ulsan)
  • 원성필 (울산대학교 기계공학부)
  • Received : 2014.07.29
  • Accepted : 2014.09.03
  • Published : 2014.11.10

Abstract

The objective of this study is to theoretically analyze the performance of an open wet air-cycle refrigeration system, which nowadays is increasingly generating environmental concern. The temperature and relative humidity of the outside air are selected as the most important parameters. As the temperature and relative humidity of the outside air increase, the pressure ratio of the ACM compressor is determined to be nearly constant, the air temperature at the exit of the system increases, and the amount of condensed water, the cooling capacity, the COP, and the total entropy production rate increase overall. The effects of the effectiveness of the heat exchanger and the efficiency of the turbine on the performance are greater than that of the efficiency of the ACM compressor. Also, the performance of the wet air-cycle refrigeration system with two heat exchangers is enhanced, with a high COP and low total entropy production rate, compared to the system with a single heat exchanger.

Keywords

References

  1. Kim, Y. M., 2005, Air cycle refrigeration technology, Journal of the Korea Society of Mechanical Engineers, Vol. 45, No. 8, pp. 23-25.
  2. Bhatti, M. S., 1998, Open air cycle air conditioning system for motor vehicles, SAE Paper 980289.
  3. Spence, S. W. T., Doran, W. J., and Artt, D. W., 2004, Design, construction and testing of an air-cycle refrigeration system for road transport, International Journal of Refrigeration, Vol. 27, No. 5, pp. 503-510. https://doi.org/10.1016/j.ijrefrig.2004.02.003
  4. Spence, S. W. T., Doran, W. J., and Artt, D. W. and McCullough, G., 2005, Performance analysis of a feasible air-cycle refrigeration system for road transport, International Journal of Refrigeration, Vol. 28, No. 3, pp. 381-388. https://doi.org/10.1016/j.ijrefrig.2004.08.005
  5. Wang, X. and Yuan, X., 2007, Reuse of condensed water to improve the performance of an air-cycle refrigeration system for transport applications, Applied Energy, Vol. 84, No. 9, pp. 874-881. https://doi.org/10.1016/j.apenergy.2007.01.018
  6. Kim, J. J. and Kim, T. S., 2006, Design parameter analysis of a reverse Brayton cycle refrigerator using natural working fluids, Proceedings of the SAREK 2006 Winter conference, pp. 417-422.
  7. Kim, J. J. and Kim, T. S., 2007, Part load analysis of a reverse brayton cycle refrigerator using natural working fluids, Proceedings of the SAREK 2007 Summer conference, pp. 127-132.
  8. Won, S. P., 2012, Performance analysis of an air-Cycle refrigeration system, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 24, No. 9, pp. 671-678. https://doi.org/10.6110/KJACR.2012.24.9.671
  9. Conceicao, S. T. and Turcio, W. H. L., 2007, Thermodynamic study of aircraft air conditioning air cycle machines : 3-wheel x 4-wheel, SAE Paper 2007-01-2579.
  10. Zhao, H., Zhu, Y. and Chen, S., 2009, Experimental study on the performance of an aircraft environmental control system, Applied Thermal Engineering, Vol. 29, No. 16, pp. 3284-3288. https://doi.org/10.1016/j.applthermaleng.2009.05.002
  11. ASHRAE, 2009, ASHRAE Handbook-Fundamentals.

Cited by

  1. Recent Progress in Air-Conditioning and Refrigeration Research: A Review of Papers Published in the Korean Journal of Air-Conditioning and Refrigeration Engineering in 2014 vol.27, pp.7, 2015, https://doi.org/10.6110/KJACR.2015.27.7.380