Theoretical Analysis of a Recuperative Refrigeration Dehumidifier

열회수 냉각 제습기의 이론적 해석

  • Kim, Dong-Seon (Department of Mechanical Engineering, Korea National University of Transportation)
  • 김동선 (한국교통대학교 기계공학과)
  • Received : 2013.10.11
  • Accepted : 2013.12.01
  • Published : 2014.01.10

Abstract

A refrigeration dehumidifier with a recuperative heat exchanger is theoretically analyzed. The recuperative heat exchanger is located between the two air streams from and to the dehumidifying coil, and reduces the sensible heat load in dehumidification process. A simple model is developed to predict performance of the dehumidifier. The model predicts that the recuperative heat exchanger is effective especially in the low humidity condition, where the sensible heat load is relatively large. It is predicted that, by adopting a recuperative heat exchanger, a maximum 30~110% increase in COP is possible for indoor air at $27^{\circ}C$, and 40~60% relative humidity.

Keywords

References

  1. Electronic Times Internet, 2013, http://www.etnews.com/ news/home_mobile/living/2767543_1482.html.
  2. Seo, J. N., Kim, Y. I., and Park, S. T., 2010, A cycle analysis for studying of the effect of inlet condition, regeneration condition and rotor rotation rate on hybrid dehumidifier, Proc. SAREK Summer Conf., pp. 1018-1022.
  3. Carrington, C. G., Bannister, P., and Liu, Q., 1995, Performance analysis of a dehumidifier using R134a, Int. J. Refrig., Vol. 8, pp. 477-485.
  4. Yau, Y. H. and Tucker, A. S., 2003, The performance study of a wet six-row heat-pipe heat exchanger operating in tropical buildings, Int. J. Energy Res., Vol. 27, pp. 187-202. https://doi.org/10.1002/er.867
  5. Lowrey, S., Carrington, G., Sun, Z., and Cunningham, M., 2012, Experimental investigation of geared domestic refrigerative dehumidifier performance in New Zealand household climates, Int. J. Refrig., Vol. 35, pp. 750-756. https://doi.org/10.1016/j.ijrefrig.2012.01.018
  6. Liang, C. H., Zhang, L. Z., and Pei, L. X., 2010, Independent air dehumidification with membrane-based total heat recovery : Modeling and experimental validation, Int. J. Refrig., Vol. 33, pp. 398-408. https://doi.org/10.1016/j.ijrefrig.2009.09.016
  7. McLinden, M. O., Klein, S. A., Lemmon, E. W., and Peskin, A. P., 1998, Thermodynamic properties of refrigerants and refrigerant mixtures database, REFPROP V.6.01, NIST.
  8. Kays, W. M. and London, A. L., 1998, Compact heat exchangers, 3rd ed., Krieger Pub. Co.
  9. Chung, H. J., Lee, J. S., Kang, H., and Kim, Y. C., 2012, Experimental study on the performance characteristics of a plastic film material rotary regenerator, Proc. 2012 KSME Summer Conf., pp. 82-83.

Cited by

  1. Recent Progress in Air-Conditioning and Refrigeration Research: A Review of Papers Published in the Korean Journal of Air-Conditioning and Refrigeration Engineering in 2014 vol.27, pp.7, 2015, https://doi.org/10.6110/KJACR.2015.27.7.380