DOI QR코드

DOI QR Code

The survey on odor emission characteristics in a sewage treatment plant by using passive samplers

Passive sampler를 이용한 하수처리시설에서 공정별 악취배출특성의 조사 연구

  • Kim, Han-Soo (Department of Environmental Engineering, Daejeon University) ;
  • Lee, Suk-Jun (Department of Environmental Engineering, Daejeon University) ;
  • Lee, Yong-Jeong (Department of Environmental Engineering, Daejeon University) ;
  • Kim, Sun-Tae (Department of Environmental Engineering, Daejeon University)
  • Received : 2013.12.28
  • Accepted : 2014.03.17
  • Published : 2014.03.30

Abstract

This research is carried out to investigate the odor emission characteristics in a sewage treatment plant. The plant was divided into four areas (boundary areas, sewage treatment processes, sludge treatment processes and odor treatment plants), and measured around 27 sampling points. Odor characteristics from each areas were evaluated by air dilution olfactory method and $NH_3/SO_2/VOCs$ passive sampler, mainly in terms of spatial distribution. The main odor emission sources were found out to be dewatering plant (S-4) of sludge, sludge transshipment place(S- 5), and the outlet of odor treatment plant (B-2, B-3). The correlation between dilution number (OU) and ammonia concentration of passive sampler appeared to be low; correlation coefficient 0.49, but correlation coefficient for the results of sulfur dioxide and toluene were very high, 0.95 and 0.93, respectively. These results indicate that odor compounds form sewage treatment facility are mainly due to sulfur compounds and volatile organic compounds.

Keywords

References

  1. Jeon, J. M., Seo, Y. S., Jeong, M. H., Lee, H. S., Lee, M. D., Han, J. S., Kang, B. W., 2010. The emission characteristics of odor compounds from environment fundamental facilities. Korea Journal of Odor Research and Engineering 9(2), 80-89.
  2. Jung, S. H., Lee, E. H., Jeoung, Y. D., Kim, Y. S., 2008. Removal of malodor from sewage treatment plant using biofilter with microbial catalyst. Korea Journal of Odor Research and Engineering 7(2), 60-67.
  3. Kim, J. W., Sekyama, K. K., Lee, D. W., Kim, H. O., 2006. Odors from wastewater treatment plants. Korea Journal of Odor Research and Engineering 5(3), 180-192.
  4. Ko, B. C., Lee, J. K., Lee, Y. S., Lee, M. G., Kam, S. K., 2012. A study on odor emission characteristics of domestic sewage treatment facilities using composite odor concentration and hydrogen sulfide concentration. Journal of the Environmental Sciences 21(11), 1379-1388. https://doi.org/10.5322/JES.2012.21.11.1379
  5. Ko, B. C., Park, Y. H., Kim, D. I., Lee, M. G., Kam, S. K., 2013. Odor removal characteristics of biofilters in domestic sewage treatment facilities analyzing composite odor and odor quotient. Journal of the Environmental Sciences 22(1), 109-117. https://doi.org/10.5322/JES.2013.22.1.109
  6. Lee, H. D., Kang, D. J., Lee, M. H., Kang, D. H., Oh, K. J., 2012. Removal efficiency of the deodorization equipment and characteristics of malodor during the process in cotreatment of sewage and food waste of Su-young wastewater treatment plant in Busan. Clean Technology 18(4), 379-289. https://doi.org/10.7464/ksct.2012.18.4.379
  7. Lee, T. Y., Kim, D. Y., Kim, J. J., Lee, J. K., 2009. Physicochemical characteristics and estimation of $H_2S$ emission rate from municipal solid waste at the environmental facilities in Busan city. Korea Geo-Environmental Society 10(2), 13-20.
  8. Ministry of Environment (MOE), 2012b. Installation of public sewage project work instruction.
  9. Nam, J. M., Kim, S. H., Rim, J. M., 2010. Innovation of the technical diagnosis technique for performance analysis and efficiency improvement of public sewage treatment plant. Journal of the Environment 7(1), 55-56.
  10. Seo, B. R., Jeon, H. S., Park, Y. S., Yun, B. R., Jang, T. H., Kim, T. O., 2013. The emission characteristics and management of odor compounds from public sewage treatment facility. Korea Journal of Odor Research and Engineering 12(3), 97-109. https://doi.org/10.11161/jkosore.2013.12.3.97