DOI QR코드

DOI QR Code

Performance Analysis of a Low-Depth Unit-Type Ground Heat Exchanger using Numerical Simulation

수치해석을 통한 저심도 유닛형 지중열교환기의 성능 검토

  • Oh, JinHwan (Department of Architecture, Graduate School, Pusan National University) ;
  • Seo, JangHoo (School of Architecture, Kookmin University) ;
  • Na, Yujin (Department of Architecture, Pusan National University)
  • 오진환 (부산대학교 건축공학과 대학원) ;
  • 서장후 (국민대학교 건축학부) ;
  • 남유진 (부산대학교 건축공학과)
  • Received : 2014.12.09
  • Accepted : 2015.01.30
  • Published : 2015.03.10

Abstract

Recently, ground source heat pump (GSHP) systems have attracted much attention, according to the enhanced social demand of renewable energy. GSHP systems can achieve higher coefficient of performance than the conventional air-source heat pump systems by utilizing stable underground temperature. However, the initial cost of GSHP system is higher than that of the conventional systems, especially, in the small-size buildings. Therefore, it is necessary to develop small-size ground heat exchanger with low cost and quick installation. In this study, a unit-type ground heat exchanger was developed and heat exchange rate was calculated by the numerical simulation. As a result, 27.45 W/m of heat exchange rate was acquired in the condition of $0.5m{\times}0.2m{\times}2m$ unit.

Keywords

References

  1. Hwang, S. H. and Nam, Y. J., 2010, A Study on Development of a Ground-Source Heat Pump System Utilizing Cast-in-place Concrete Pile Foundation of a Building, Journal of SAREK, Vol. 22, pp. 641-647.
  2. Nam, Y. J. and Chae, H. B., 2013, Prediction of the Heat Exchange Rate for a Horizontal Ground Heat Pump System Using a Ground Heat Transfer Simulation, Korea Journal of Air-Conditioning and Refrigeration Engineering, Vol. 25, pp. 297-302. https://doi.org/10.6110/KJACR.2013.25.6.297
  3. Hwang, Y. H., Lee, K. H., and Cho, S. W., 2012, Ground-Pipe Type and Length for Applicability of Geothermal Heat Pump in Small Residential Houses, Journal of KIAEBS, Vol. 6, pp. 216-221.
  4. Hwang, S. H. and Song. D. S., 2010, A study on the heat transfer performance according to ground heat exchanger types, Journal of KIEAE, Vol. 10, pp. 75-80.
  5. Sohn, B. H., Jung. K. S., and Choi, H. S., 2013, Performance prediction of geothermal heat pump(GHP) system using cast-in-place energy piles, Journal of SAREK, Vol. 25, pp. 28-36.
  6. Naili, N., Hazami, M., Kooli, S., and Farhat, A., 2015, Energy and exergy analysis of horizontal ground heat exchanger for hot climatic condition of northern Tunisia, Geothermics, Vol. 53, pp. 270-280. https://doi.org/10.1016/j.geothermics.2014.07.004
  7. Park, S. W., Lee, D. S., Choi, H. J., Jung, K. S., and Choi, H. S., 2014, Relative constructability and thermal performance of cast-in-place concrete pile : Coil-type GHEX(ground heat exchanger), Energy, pp. 1-11.
  8. Park, H. K., Lee, S. R., Yoon, S., and Choi, J. C., 2013, Evalution of thermal response and performance of PHC energy pile : field experiments and numerical simulation, Applied Energy, pp. 12-24.
  9. Gao, J., Zhang, X., Liu, J., Shan, K., and Yang, J., 2008, Thermal performance and ground temperature of vertical pile-foundation heat exchangers : A case study, Applied Thermal Engineering, Vol. 28, pp. 2295-2304. https://doi.org/10.1016/j.applthermaleng.2008.01.013
  10. Nam, Y. J., 2011, Numerical analysis for the effect of ground and groundwater conditions on the performance of ground source heat pump system, Journal of SAREK, Vol. 23, No. 5, pp. 321-326.
  11. Nam Y. J., Ooka, R., and Hwang, S. H., 2008, Development of a numerical model to predict heat exchange rates for a ground-source heat pump system, Energy and Buildings, Vol. 40, pp. 2133-2140. https://doi.org/10.1016/j.enbuild.2008.06.004
  12. Sohn, B. H., 2012, Performance analysis of groundcoupled heat pump system with slinky-type horizontal ground heat exchanger, Journal of SAREK, Vol. 24, No. 3, pp. 230-239.
  13. Gonzalez, R. G., Verhoef, A., Vidale, P. L., Main, B., and Gan, G., 2012, Interactions between the physical soil environment and a horizontal ground coupled heat pump, for a domestic site in the UK, Renewable Energy, Vol. 44, pp. 141-153. https://doi.org/10.1016/j.renene.2012.01.080

Cited by

  1. Recent Progress in Air-Conditioning and Refrigeration Research : A Review of Papers Published in the Korean Journal of Air-Conditioning and Refrigeration Engineering in 2015 vol.28, pp.6, 2016, https://doi.org/10.6110/KJACR.2016.28.6.256