A Design Optimization on Coupling Joint between Exhaust Chimney of Electricity Generator and Electromagnetic Pulse (EMP) Shield

EMP 차폐를 위한 비상발전기 연도의 최적 형상 결정

  • Received : 2015.11.17
  • Accepted : 2015.12.19
  • Published : 2015.12.31

Abstract

The article presents a parametric study on geometrical design optimization for coupling the joint between a large exhaust air chimney and electromagnetic pulse (EMP) shield for gas turbine electricity generator. We conducted computational fluid dynamics (CFD) simulations on hydraulic diameters of waveguide below cutoff(WBC) ranges 800mm~1025mm, the connection distance ranges 150~450mm, and exhaust gas flow velocities at 15, 20, and 25m/s. The results show that the diameter of main chimney, connection distance, and exhaust gas velocity had impacts on flow stream at the EMP shield. To provide a fully developed stream line at three different flow velocity cases, the WBC diameter and distance of connection should be larger than 1050mm and longer than 300mm, respectively.

본 논문에서는 EMP 차폐를 위한 WBC 배열이 설치된 대형 비상발전기 연도의 최적형상을 결정하는 것을 목표로 연구를 진행하였다. 시뮬레이션은 WBC 배열의 외부관경이 800, 850, 900, 1050mm 및 1250mm를 대상으로 하였으며 기본연도와의 접속길이를 150, 300, 450 mm, 연도의 유속은 15, 20, 25m/s로 하였다. EMP 차폐를 위한 WBC 배열을 연도에 설치하는 경우 WBC 배열의 외부관경, Main 연도와의 접속길이가 배기가스 흐름에 큰 영향을 미치는 것으로 나타났다. WBC 배열의 외부관경이 1050, 1250mm이고 접속길이가 300, 450mm이면 도파관 배열에서 배기가스의 평균속도와 최고속도를 만족시키는 것으로 나타났다.

Keywords

References

  1. S.K.Pang, Y.T.Chae, J.G.Yook, Ynna Kim, Sangin Kim, 2015, Air Stream around EMP Protective Device for Emergency Power System, Proceedings of the Geothermal Energy Engineers, Vol. 1, Korea Society of Geothermal Energy Engineers, Daejeon, Korea, pp.41-44.
  2. S. J. Lee, (2014), Demand Response Controls using On-site Electricity Generator for Emergency, KOREA ENERGY ECONOMICS INSTITUTE
  3. KOREA OCCUPATIONAL SAFETY & HEALTH AGENCY, KOSHA CODE E-84-2011, Technical Report for Design and Application of Emergency Electricity Supplier.