Active Damping of LLCL Filters Using PR Control for Grid-Connected Three-Level T-Type Converters

  • Alemi, Payam (Department of Electrical Engineering, Yeungnam University) ;
  • Jeong, Seon-Yeong (Department of Electrical Engineering, Yeungnam University) ;
  • Lee, Dong-Choon (Department of Electrical Engineering, Yeungnam University)
  • Received : 2014.10.10
  • Accepted : 2014.12.16
  • Published : 2015.05.20

Abstract

In this paper, an active damping control scheme for LLCL filters based on the PR (proportional-resonant) regulator is proposed for grid-connected three-level T-type PWM converter systems. The PR controller gives an infinite gain at the resonance frequency. As a result, the oscillation can be suppressed at that frequency. In order to improve the stability of the system in the case of grid impedance variations, online grid impedance estimation is applied. Simulation and experimental results have verified the effectiveness of the proposed scheme for three-phase T-type AC/DC PWM converters.

Keywords

I. INTRODUCTION

In recent years, voltage source converters (VSC) have been widely employed for grid-connected applications with the advantage of bidirectional power flow and its ability to control the voltage and power factor. In particular, multilevel converters such as T-type three-level inverters have been used due to their higher performance and efficiency when compared with the two-level converters [1]-[3]. To suppress switching harmonics, a large size filter inductor is needed in the VSC. However, this deteriorates the system dynamic performance and increases the cost of the inductor in high power applications.

Due to the advantages in terms of cost and dynamics, LCL filters are preferred over L filters for grid-connected PWM converters since smaller inductors can be used in the LCL filters. However, there are drawbacks of LCL filters such as the resonance phenomena and the complex control algorithm [4]-[7]. To suppress the filter resonance, a number of passive and active damping methods have been proposed [8]-[16]. The passive damping methods are simple and reliable, but power loss is an issue especially for high power applications [8]-[10]. On the other hand, the active damping schemes do not increase power losses, but the control algorithm is modified to suppress resonance [11]-[17]. In [12], [13], an active damping method based on a virtual resistor has been proposed. However, an extra capacitor current sensor is required. In [14], a genetic algorithm has been applied to tune the notch filter for the active damping of LCL filters. Although no extra sensor is needed, the optimization algorithm is complicated. The PR regulator has been discussed for LCL filters in [15], [16]. However, the grid impedance variation has not been investigated which is an issue in the case of a variable grid impedance.

To reduce the inductor size in LCL filters, a new structure for the LLCL filters of single-phase VSCs has been proposed [18]. To suppress the resonance of the LLCL filters, the passive damping method has been employed, where an additional resistor was used [9]-[11].

This paper is an extended version of [16], where an active damping method based on the PR control has been proposed for the LLCL filters of three-level T-type converters. To suppress the resonance in the case of variable grid impedances, the online grid impedance estimation method is applied. In addition, the system stability is analyzed to show the validity of the proposed control algorithm. The effectiveness of the proposed method is verified by simulation and experimental results obtained for a three-level T-type converter.

 

II. SYSTEM DESCRIPTION

A. Three-Level T-type AC/DC PWM Converters

A three-level T-type AC/DC PWM converter is shown in Fig. 1. It is connected to the grid through LLCL filters. The grid is modeled as a sinusoidal voltage source with variable line impedances. A resistive load is connected to the DC output terminal of the converter. For the PWM converter, the voltage equations are expressed in the synchronous reference frame as [19]:

Fig. 1.Grid-connected three-level T-type converters with LLCL filters.

where:

By aligning the q-axis of the synchronous reference frame to the grid voltage, ede = 0. The DC-link voltage dynamics can be expressed as:

where:

where the losses in the filter and the converter are neglected.

B. LLCL Filters

In LLCL filters, the transfer functions of the grid and converter currents to the converter voltage are expressed as:

where:

From (4) and (5), the resonance frequency in the LLCL filters is given by:

The frequency responses of the grid and converter currents to the converter voltage are shown in Fig. 2(a) and (b), respectively. It can be seen that the impedance of the LLCL filters is very low near the switching frequency due to the series inductor in the capacitor branch.

Fig. 2.Bode plots of transfer functions in LCL and LLCL filters. (a) G1(s) = Ig(s)/Vi(s). (b) G2(s) = Ic(s)/Vi(s).

C. Parameter Design of LLCL Filters

In the design of the filter, some limitations on the parameter values should be considered as follows [6], [8]:

 

III. PROPOSED ACTIVE DAMPING CONTROL

Fig. 3 shows the control block diagram of the grid-connected T-type converter with the LLCL filters, where the PR control is applied for active damping.

Fig. 3.Control block diagram of the grid-connected PWM converter with LLCL filters.

A. Active Damping Control

The PR controller is operated in the abc-reference frame, where the steady-state error is eliminated at the specified resonance frequency. The transfer function of the PR controller is given as

where:

The magnitude and phase characteristics of the open-loop transfer function for the PR controller with respect to the different resonant gains are illustrated in Fig. 4. It can be seen that the higher resonant gains can eliminate the steady-state error. However, this leads to a wider bandwidth.

Fig. 4.Bode plots of the resonant controller for different gains (Kr).

B. Grid Impedance Estimation

To suppress the resonance effectively, the grid impedance needs to be known. In this study, an online estimation of the grid impedance is applied to find the total inductance on the grid side of the LLCL filters [20]. When a voltage component of the specified frequency is added to the PWM voltage reference, a harmonic current component is incurred at the same frequency. Next, the Discrete Fourier analysis for the specific injected harmonic component is applied as:

where:

point n

Then, the harmonic current and voltage components are obtained from (12). From these the grid impedance at the specified harmonic frequency is calculated as:

where:

The grid impedance in terms of the fundamental frequency is obtained by:

Fig. 5 illustrates variations of the filter resonance frequency according to variations of the grid impedance. By increasing the grid inductance from Lgrid = 0 to 0.5mH the filter resonance frequency, fres, varies from 1.9 kHz to 1.48 kHz.

Fig. 5.Bode plots of transfer functions of LLCL filters for different values of grid inductance.

 

IV. STABILITY ANALYSIS

To determine the feasibility of the proposed active damping method, the system stability is analyzed. The overall current control scheme is depicted in Fig. 6. Since the PI current controller (GPI(s) = Kp + Ki/s) is used in the synchronous reference frame, its equivalent form for the transfer function, GPR_f(s), in the stationary reference frame is given by:

Fig. 6.The proposed closed-loop current control in stationary reference frame.

where:

A BPF (band-pass filter) is needed for the PR controller to damp the filter resonance, where the cut-off frequency is equal to the resonance frequency of the LLCL filters. The transfer function of the BPF is expressed as:

where:

Therefore, the transfer function of the current controller, Gc(s), is the sum of GPR_f(s) in (15) and the multiplication of GPR_r(s) and GBPF(s) in (11) and (16) respectively, which can be expressed as:

The stability is evaluated in the Z-domain, where one sampling delay of the digital processing and one-half a sampling delay of the PWM converters are involved in the PWM block, which is expressed as:

Then, the open-loop transfer function of the current control system is expressed as:

To analyze the frequency response of the proposed current control system, the closed-loop transfer function in (20) is investigated.

The root loci for the proposed current control system are illustrated in Fig. 7. In Fig. 7(a), the root loci is plotted at the switching frequency of fsw= 4 kHz. The control system is stable since all of the poles are placed inside the unit cycle. As the switching frequency is increased, the stability may be degraded. However, by tuning the controller gains, the system can still be stable at fsw= 6 kHz and fsw= 8 kHz, as illustrated in Fig. 7(b) and (c), respectively. A further increase of the switching frequency may cause instability since the system poles are placed outside the unit cycle.

Fig. 7.Root loci of the proposed current control system. (a) fsw= 4 kHz. (b) fsw= 6 kHz. (c) fsw= 8 kHz.

The frequency response of (19) is illustrated in Fig. 8 where the controller gains are Kp = 9, Ki = 3000, Kpr = 6, Kir = 50 and the bandwidth of the controller is approximately 500 Hz, which results from the definition of GM = −3dB in the closed-loop control system. A band-pass-filer (BPF) with a cut-off frequency of 1.9 kHz and a bandwidth of 200 Hz are employed to extract the resonant components in the grid currents. In order to guarantee stability, a phase margin of PM > 45° and a gain margin GM > 6dB are generally desirable [13], [21]. Fig. 8 shows that the gain and phase margins of the open-loop current control system are 13 dB and 46°, respectively.

Fig. 8.Bode plot of the open-loop current control system.

Fig. 9 shows the step responses of the closed-loop system in (20), where a resonance phenomenon does not appear.

Fig. 9.Step response of the closed-loop current control system.

 

V. SIMULATION RESULTS

A simulation is performed for the three-level T-type PWM converter. The simulation parameters are listed in Table I. The different parameters of the filters are shown in Table II.

TABLE IPWMCONVERTER PARAMETERS

TABLE IIFILTER PARAMETERS

Fig. 10 illustrates the performance of the grid impedance estimation. The estimated and real values of the grid inductance are shown in (a), where the estimation error is less than 5%. In (b), the magnitude of the injected harmonic and its frequency are shown. The distortion in the grid current, due to the harmonic injection, appears as shown in (c). In (d), the resonance frequency of the LLCL filters for different grid impedances is illustrated, where the resonance frequency varies from 1.9 kHz in the case of zero grid impedance to 1.48 kHz in the case of a grid impedance of 0.5 mH.

Fig. 10.Grid impedance estimation. (a) Grid inductance. (b) Harmonic voltage. (c) Grid current. (d) Resonance frequency.

Fig. 11 shows the grid and converter currents and the FFT spectra in the case I (L1 =1.2 mH, L2 = 0.8 mH) of LCL filters. The magnitude of the dominant harmonic component in the grid current is lower than 0.1 A (0.18% of the fundamental component). The total harmonic distortion (THD) factors are listed in Table III. For this Case I the THD is 2.91%.

Fig. 11.Grid and converter currents with FFT spectra in case I of LCL filters: L1 =1.2 mH, L2 =0.8 mH.

TABLE IIITHD AND SIDEBAND HARMONIC MAGNITUDE OF THE GRID CURRENT IN DIFFERENT CASES

Case II of the LCL filters (L1 =1.2 mH, L2 = 0.35 mH) is illustrated in Fig. 12, where the dominant harmonic magnitude in the grid current is lower than 0.3 A (0.56 % of the fundamental current) with a THD of 5.12%. It is obvious that Case II of the LCL filters does not meet the requirement of the IEEE standard 519-1992.

Fig. 12.Grid and converter currents with FFT spectra in case II of LCL filters: L1 =1.2 mH, L2 =0.35 mH.

Case III of the LLCL filters (L1 =1.2 mH, L2 = 0.35 mH, and Lf = 0.08 mH) is shown in Fig. 13, where the magnitude of the dominant harmonic in the grid current is lower than 0.92 A (0.17 % of the fundamental component) with a THD of 2.64% (Table III).

Fig. 13.Grid and converter currents with FFT spectra in case III of LLCL filters: L1 =1.2 mH, L2 =0.35 mH, Lf =0.08 mH.

 

VI. EXPERIMENTAL RESULTS

To verify the proposed damping control, experiments have been conducted on a 3-kW converter system. A 32-b DSP chip (TMS320F28335) is used for the main controller. The parameters of the three-level T-type converter are listed in Table. IV. The PWM frequency of the converter is 5 kHz and the dead time is set to 2 µs. For the IGBT module (4MBI300VG-120R-50), two gating drivers have been employed such as VLA513-01R for the mid-point IGBTs and VLA542-01 for the leg IGBTs. For the reduced-scale system of the simulation, the LLCL filters are redesigned by the same procedure described in section II (Table. V). Fig. 14 shows the three-level T-type PWM converter used for the tests.

Fig. 14.Three-level T-type PWM converter.

TABLE IVPWMCONVERTER PARAMETERS

TABLE VFILTER PARAMETERS

The grid and converter currents and the FFT spectra are shown in Fig. 15, for Case I of the LCL filters (L1 =2 mH, L2 = 1 mH) where the magnitude of the dominant harmonic component in the grid current is lower than 0.021 A (0.2% of the fundamental component) with a THD of 3.72%.

Fig. 15.Grid and converter currents with FFT spectra in the case I of LCL filters (L1=2 mH, L2=1 mH).

Fig. 16 illustrates the same waveforms as in Fig. 15, in Case II of the LCL filters (L1 =2 mH, L2 = 0.4 mH), where the dominant harmonic magnitude in the grid current is lower than 0.052 A (0.46 % of the fundamental current) with a THD of 4.04%. It is obvious that Case II of the LCL filters does not meet the requirement of the IEEE standard. In Case III of the LLCL filters (L1 =2 mH, L2 = 0.4 mH, and Lf = 0.1 mH), as shown in Fig. 17, the magnitude of the dominant harmonic in the grid current is lower than 0.015 A (0.13 % of the fundamental component) with a THD of 2.47% (Table VI).

Fig. 16.Grid and converter currents with FFT spectra in the case II of LCL filters: L1=2 mH, L2=0.4 mH.

TABLE VITHD AND SIDEBAND HARMONICS MAGNITUDE OF THE GRID CURRENT IN DIFFERENT CASES

Fig. 17.Grid and converter currents with FFT spectra in case III of LLCL filters: L1=2 mH, L2=0.4 mH, Lf=0.1 mH.

Fig. 18 shows the grid phase currents and FFT spectra in the case of different grid impedances. Even though the grid impedance is changed from 0.1 mH to 0.2 mH, the PR controller can suppress the resonance effectively with the estimated grid impedance. In addition, a THD of about 2.4% in the grid currents is within the acceptable level.

Fig. 18.Grid currents and FFT spectra with LLCL filters. (a) Lgrid = 0.1 mH. (b) Lgrid = 0.2 mH.

Fig. 19 shows the converter performance in the case of a resistive load application, where the grid current and the q-axis converter current are shown in (a) and (b), respectively. The DC-link voltage is fluctuated at the point where the converter q-axis current changes abruptly, where the undershoot in the DC-link voltage is lower than 10% as shown in (c). The converter phase current is illustrated in (d). As can be seen, it is more distorted than the grid current.

Fig. 19.Converter control performance with LLCL filters. (L1 =2 mH, L2 = 0.4 mH, and Lf = 0.10 mH). (a) Grid phase current. (b) Converter q-axis current. (c) DC-link voltage. (d) Converter phase current.

Fig. 20 shows the performance of the converter in the case of unbalanced grid voltages, where one phase-voltage of the grid is decreased by 20% as shown in (a). The grid phase current in the case of resistive load variations is shown in (b), where the switching ripples meet the IEEE standard of 0.3%. The fluctuations in the DC-link voltage do not exceed 10 % as shown in (c), which is acceptable under this condition.

Fig. 20.Converter control performance with LLCL filters in the case of 20% drop in grid voltage. (L1 =2 mH, L2 = 0.4 mH, and Lf = 0.1 mH). (a) Grid three-phase voltages. (b) Grid phase current (c) DC-link voltage.

 

VII. CONCLUSION

In this paper, an active damping method using a PR controller has been proposed for the LLCL filters connected to the three-level T-type PWM converter. In addition, the grid impedance has been estimated online to compensate for the resonance frequency of the filter in the case of a variable grid impedance. The damping effect of the PR controller on LLCL filters has been verified by simulation and experimental results. In the LLCL filters, the grid-side inductor has been reduced by 60%, when compared with the LCL filters, from 0.8 mH to 0.35 mH in the simulation and from 1 mH to 0.4 mH in the experiment. In this case, the THD and dominant harmonic component of the grid current have met the IEEE standard. It has been shown that the control performance for the LLCL filters is satisfactory both in the transient state and under grid voltage unbalances.

References

  1. J. Rodriguez, J.-S. Lai, and F. Z. Peng, “Multilevel inverters: A survey of topologies, controls, and applications,” IEEE Trans. Ind. Applicat., Vol. 49, No. 3, pp. 724-738, Aug. 2002.
  2. M. Schweizer, and J. W. Kolar, “Design and implementation of a highly efficient three-level T-type converter for low-voltage applications,” IEEE Trans. Power Electron., Vol. 28, No. 2, pp. 899-907, Feb. 2013. https://doi.org/10.1109/TPEL.2012.2203151
  3. M. Liserre, F. Blaabjerg, and S. Hansen, “Design and control of an LCL-filter-based three-phase active rectifier,” IEEE Trans. Ind. Applicat., Vol. 41, No. 5, pp. 1281-1291, Sep./Oct. 2005. https://doi.org/10.1109/TIA.2005.853373
  4. E. Twining and D. G. Holmes, “Grid current regulation of a three- phase voltage source inverter with an LCL input filter,” IEEE Trans. Power Electron., Vol. 18, No. 3, pp. 888-895, Feb. 2003. https://doi.org/10.1109/TPEL.2003.810838
  5. J. Dannehl, C. Wessels, and F. Fuchs, “Limitations of voltage-oriented PI current control of grid-connected PWM rectifiers with LCL filters,” IEEE Trans. Ind. Electron., Vol. 56, No. 2, pp. 380-388, Feb. 2009. https://doi.org/10.1109/TIE.2008.2008774
  6. I. J. Gabe, V. F. Montagner, and H. Pinheiro, “Design and implementation of a robust current controller for VSI connected to the grid through an LCL filter,” IEEE Trans. Power Electron., Vol. 24, No. 6, pp. 1444-1452, Jun. 2009. https://doi.org/10.1109/TPEL.2009.2016097
  7. Z. Zeng, J.-Q. Yang, S.-L. Chen, and J. Huang, “Co-design of the LCL filter and control for grid-connected inverters,” Journal of Power Electronics, Vol. 14, No. 4, pp. 1-10, Jul. 2014. https://doi.org/10.6113/JPE.2014.14.1.1
  8. R. P-Alzola, M. Liserre, F. Blaabjerg, R. Sebastian, J. Dannehl, and F. Wilhelm Fuchs, “Analysis of the passive damping losses in LCL-filter-based grid converters,” IEEE Trans. Power Electron., Vol. 28, No. 6, pp. 2642-2646, Jun. 2013. https://doi.org/10.1109/TPEL.2012.2222931
  9. W. Wu, Y. He, T. Tang, and F. Blaabjerg, “A new design method for the passive damped LCL and LLCL filter based single phase grid tied inverter,” IEEE Trans. Ind. Appl., Vol. 60, No. 10, pp. 4339-4349, Oct. 2013.
  10. W. Wu, Y. Sun, M. Huang, X. Wang, F. Blaabjerg, M. Liserre, and H. S.-h. Chung, “A robust passive damping method for LLCL-filter-based grid-tied inverters to minimize the effect of grid harmonic voltages,” IEEE Trans. Power Electron., Vol. 29, No. 7, pp. 3279-3289, Jul. 2014. https://doi.org/10.1109/TPEL.2013.2279191
  11. Byoung-Woong An, Chang-Pyo Hong, Hag-Won Kim, Kwan-Yuhl Cho, and Byung-Kuk Lim, “A Study on LLCL Filter to Reduce Harmonic Current of Grid Connected Power Inverter,” Transactions of Korean Institute of Power Electronics(KIPE), Vol. 19, No. 1, pp. 64-70, Feb. 2014. https://doi.org/10.6113/TKPE.2014.19.1.64
  12. P. A. Dahono, "A control method for dc-dc converter that has an LCL output filter based on new virtual capacitor and resistor concepts," in Proc. IEEE PESC, pp. 36-42, 2004.
  13. C. Wessels, J. Dannehl, and F. W. Fuchs, "Active damping of LCL filter resonance based on virtual resistor for PWM rectifiers-stability analysis with different filter parameters," in Proc. IEEE PESC, pp. 3532-3538, 2008.
  14. M. Liserre, A. Dell’Aquila, and F. Blaabjerg, “Genetic algorithm-based design of the active damping for an LCL-filter three-phase active rectifier,” IEEE Trans. Power Electron., Vol. 19, No. 1, pp. 76-86, Jan. 2004. https://doi.org/10.1109/TPEL.2003.820540
  15. R. Teodorescu, F. Blaabjerg, U. Borup, and M. Liserre, "A new control structure for grid-connected lcl pv inverters with zero steady-state error and selective harmonic compensation," in Proc. IEEE APEC'04, Vol. 1, pp. 580-586, 2004.
  16. P. Alemi and D.-C. Lee, "Active damping control of LLCL filters for three-level T-type grid converters," in Proc. IPEC 2014-ECCE Asia, pp. 1201-1206, 2014.
  17. Z. Zeng, J.-Q. Yang, S.-L. Chen, and J. Huang, “Fast transient repetitive control strategy for a three-phase LCL filter based shunt active power filter,” Journal of Power Electronics, Vol. 14, No. 2, pp. 392-401, Mar. 2014. https://doi.org/10.6113/JPE.2014.14.2.392
  18. W. Wu and F. Blaabjerg, “An LLCL power filter for single-phase grid-tied inverter,” IEEE Trans. Power Electron., Vol. 27, No. 2, pp. 782-789, Feb. 2012. https://doi.org/10.1109/TPEL.2011.2161337
  19. S.-K. Sul, Control of Electric Machine Drive Systems, IEEE Press, 2011.
  20. L. Asiminoaei, R. Teodorescu, F. Blaabjerg, and U. Borup, “A digital controlled PV-inverter with grid impedance estimation for ENS detection,” IEEE Trans. Power Electron., Vol. 20, No. 6, pp. 1480-1490, Nov. 2005. https://doi.org/10.1109/TPEL.2005.857506
  21. X.-Q. Li, X.-J. Wu, Y.-W. Geng, and Q. Zhang, “Stability analysis of grid-connected inverters with an LCL filter considering grid impedance,” Journal of Power Electronics, Vol. 13, No. 5, pp. 896-908, Sep. 2013. https://doi.org/10.6113/JPE.2013.13.5.896

Cited by

  1. Stability Analysis of Current Control based on Virtual Resistor for Single-Phase Grid Converters with LLCL Input Filters vol.21, pp.5, 2016, https://doi.org/10.6113/TKPE.2016.21.5.404
  2. A Novel Control Scheme for T-Type Three-Level SSG Converters Using Adaptive PR Controller with a Variable Frequency Resonant PLL vol.16, pp.3, 2016, https://doi.org/10.6113/JPE.2016.16.3.1176
  3. A Real-Time Method for the Diagnosis of Multiple Switch Faults in NPC Inverters Based on Output Currents Analysis vol.16, pp.4, 2016, https://doi.org/10.6113/JPE.2016.16.4.1415
  4. Stability Analysis and Improvement of the Capacitor Current Active Damping of the LCL Filters in Grid-Connected Applications vol.16, pp.4, 2016, https://doi.org/10.6113/JPE.2016.16.4.1565
  5. A three-phase community microgrid comprised of single-phase energy resources with an uneven scattering amongst phases vol.84, 2017, https://doi.org/10.1016/j.ijepes.2016.06.010