An Experimental Study on the Air Sterilization Performance of A Reflective Electro Magnetic Energy System

Reflective Electro Magnetic Energy(REME)를 이용한 공기살균시스템의 성능평가에 관한 실험적 연구

  • 홍진관 (가천대학교 설비소방공학과) ;
  • 임가연 (가천대학교 대학원)
  • Received : 2016.09.21
  • Accepted : 2016.11.15
  • Published : 2016.12.10

Abstract

From the point of view to prevent airborne infection-related diseases such as H1N1, SARS, and MERS, an actual application of air cleaning and purification systems including technologies like UVGI has become increasingly important. Recently, an air purification system using REME (Reflective Electro Magnetic Energy) developed in the U.S. is applied for indoor air purification and sterilization technology to counteract the outbreak of new airborne infections. In this study, an air sterilization performance experiment using REME was carried out. The results verified that air sterilization performance in the case of installing a REME system in a medical center was 31%, namely the number of floating bacteria decreased by 31% after only a five-day operation. In addition, the number of culture collections in the REME operating air conditioning systems using nonpathogenic Geobacillus stearothemophilus as a biological indicator decreased maximally to 67%. A field application of REME technology will be useful to prevent airborne infection-related diseases, especially in response to public health crises due to the advent of emerging diseases.

Keywords

References

  1. Ministry of Health and Welfare & Korea Center for Disease Control and Prevention, MERS Portal.
  2. Choi, S. G. and Hong, J. K., 2005, The Study on the Performance Estimation of UVC Air Sterilizer for Preventing Transmission of Air Borne Contagion, Journal of SAREK, Vol. 17, No. 6, pp. 581-586.
  3. Indoor Air Quality, RGF Environmental Air Purification Systems, 2015.
  4. Kim et al., 2012, The Study on Energy Saving Method through Improved Air Conditioning System for Special Contaminant Laboratory Facilities, KCDC Report.
  5. Occupational Health Guideline for Hydrogen Peroxide, OSHA Regulations, 1978.
  6. Self-Contained Glass Ampoule for Steam Sterlization, Biological & Chemical Indicators, WooJung BSC Technical Materials, 2016.
  7. Statement of Verification for Biosafety Level 3 and 4 Laboratory, Ministry of Health and Welfare & Korea Center for Disease Control and Prevention, 2014.
  8. SAREK : Handbook, 2011, Airconditioning, Vol. 2, No. 4, Ch. 2, Measurement Method.
  9. ASHRAE : Handbook, 2009, Fundamentals, Ch. 11, Air Contaminants.