DOI QR코드

DOI QR Code

Implementation of a Residual Quantity Monitoring System in a Liquefied Gas Storage Tank based on Wireless Sensor Network Technology

무선센서 네트워크 기술 기반 액화가스 저장탱크 내 잔량 모니터링 시스템 구현

  • Kim, Min-Kyu (Department of Automation System, Korea Polytechnics) ;
  • Han, Hae-Jin (Department of Smart Electronic, Korea Polytechnics) ;
  • Han, Jaehwan (Medical & Biological Engineering, Kyungpook National University)
  • 김민규 (한국폴리텍대학 자동화시스템과) ;
  • 한해진 (한국폴리텍대학 스마트전자과) ;
  • 한재환 (경북대학교 의공학과)
  • Received : 2018.07.18
  • Accepted : 2018.08.13
  • Published : 2018.09.30

Abstract

This paper relates to a technology for monitoring a liquefied gas storage tank in the special gas field where demand is increasing owing to the continuous growth of related fields such as the semiconductor, display, and ICT convergence electronics industries. We have proposed a system for real - time monitoring using wireless sensor network technology, and implemented a system consisting of a sensor unit, transmitter module, and receiver module to be attached to a liquefied gas storage tank. The system was applied to LCO2 tanks among various liquefied gas storage tanks to verify the feasibility. The storage tanks employed in the experiments has capacities of 16,179 l and was 1,920 mm in inner diameter. Furthermore, the density was 1.03 g/l. The measured data were compared with reference data on the remaining gas level versus the $CO_2$ height of the surface, expressed using a conventional water meter, provided by an existing storage tank supplier. The experimental results show that the data is similar to the standard data provided by the tank supplier, and has a high accuracy and reliability within an error range of 0.03%.

Keywords

References

  1. D. J. Choi, H. I. Lim, D. H. Doh and J. R. Cho, "A study on designing a level gauge for cryogenic liquefied storage vessel by using a differential pressure sensor", J. Korean Soc. of Mar. Eng., Vol. 37, No. 4, pp. 384-390, 2013. https://doi.org/10.5916/jkosme.2013.37.4.384
  2. S. H Lee and T. W. Lee, "Deformation analysis of miniature metal bellows charged nitrogen for temperature change to cryogenic condition", J. Korean Soc. Precis. Eng., Vol. 26, No. 10, pp. 81-88, 2009.
  3. J. S. Park, H. K. Seo, S. J. Go, H. J. Park and D. J. Choi, "Design of measurement system of liquefied gas level with very low temperature", J. Korean Soc. Precis. Eng., Vol. 27, No. 5, pp. 1039-1040, 2010.
  4. H. H. Kim, G. J. Han and D. S. Han, "A study on the structural stability analysis of the cryogenic value", Proc. Korean Soc. Precis. Eng. Conf., pp. 569-570, 2008.
  5. http://www.te.com/(retrieved on 'Sensor Solution-Pressure sensor').
  6. S. H. Paik, J. Y. Lee, S. W. Jung and H. B. Park, "NDIR Multi-gas Measurement System for Air Quality Based on Wireless Sensor Network", J. Embed. Syst. Appl., Vol. 11, No. 5, pp. 299-304, 2016.
  7. S. K. Shin, J. D. Kwon, Y. D. Lee and W. Y. Chung, "Ad-hoc Home Network System using Wireless Sensor Network Technology", J. Korean Sens. Soc., Vol. 16, No. 2, pp. 142-149, 2007.
  8. http://www.chipsen.com/(retrieved on 'User Manual-Air-Bon F400SN').