DOI QR코드

DOI QR Code

Study on Multi Parameter Measurement and Analysis of Distribution High Voltage Cable Connection Part

배전용 특고압 케이블 접속재의 다변수 측정 분석 연구

  • 송기홍 (전남대학교 전기 및 반도체공학과) ;
  • 배영철 (전남대학교 전기전자통신컴퓨터공학부) ;
  • 김이곤 (전남대학교 전기전자통신컴퓨터공학부)
  • Received : 2020.11.21
  • Accepted : 2021.02.17
  • Published : 2021.02.28

Abstract

High voltage CV cables have been widely installed underground due to their convenience and urban aesthetics. However, cable accidents have occurred frequently owing to poor construction and natural degradations. This paper proposes the method to measure the multi parameter measurement for optimum diagnostics of high voltage cable connection parts and verifies its technical usefulness. This measurement is intended to diagnose degradations of cable connection parts by using simultaneous vibration and thermography as well as partial discharge(PD). The experiment in a shielded laboratory was carried out to verify the usefulness of the multi parameter measurement. The experiment defined the degradation of the cable connection part as 12 types, and produced each degradation sample. As a result of experiment, it was possible to check the correlation of vibration signals with regard to progress in some defects. In the case of thermography, the coherence with regard to the progress of some defects was found. We figure that the proposed method would be useful also in the noise environment.

고전압 CV 케이블은 편의성과 도시적 미관으로 인해 지하에 널리 설치되고 있습니다. 그러나 케이블 사고는 조립불량과 자연 열화로 인해 자주 발생하고 있다. 본 논문에서는 고전압 케이블 접속부의 최적 진단을 위한 다변수 측정 방법을 제안하고 그 기술적 유용성을 검증한다. 다변수 측정은 부분방전과 함께 진동과 열화상을 동시에 사용하여 케이블 연결 부품의 성능 저하를 진단하기 위한 기술이다. 다변수 측정의 유용성을 확인하기 위해 차폐 실험실에서 가속열화 실험을 수행하였고, 실험은 케이블 접속부의 열화를 12가지 유형으로 정의하여 각 열화 샘플을 제작하였다. 실험 결과, 진동신호 방법은 열화 진행과의 상관관계가 있는 결함 종류를 확인할 수 있었다. 열화상 검사의 경우 일부 결함의 진행과 관련하여 일관성이 발견되었다. 본 논문에서 제안된 방법은 현장에서 유용할 것으로 판단된다.

Keywords

References

  1. E. Pultrum, R. Gruntjes, and B. Verhoeven, "The value of type testing cables and accessories," CIRED 2009, The 20th International Conference and Exhibition on Electricity Distribution, Part 2, Prague, Czech Republic, June 2009.
  2. A. Mantey and G. Toman, "Plant Support Engineering : Aging Management Program Guidance for Medium-Voltage Cable Systems for Nuclear Power Plants, Revision 1," EPRI, Technical Report, 2016.
  3. E. Pultrum, M. J. M. Vanreit, "HF partial discharge detection of HV extruded cable accessories," GICABLE 95 4th international conference on insulated power cables, Paris, France, June 1995.
  4. C. Lee, "Partial Discharge Measurement in Extra High Voltage on Site," Autumn Annual Conference & Techno-Fair of KIEE, Gochang, Jeonbuk, South Korea, 2014.
  5. S. K. Aggarwal, "Literature Review of Environmental Qualification of Safety-Related Electric Cables," U.S. Nuclear Regulatory Commission(NUREG/CR-6384 BNL-NUREG-52480) vol. 1. Apr. 1996.
  6. K. Choi, "Highly sensitive partial discharge sensor with remote monitoring capabilities," J. of the Korea Institute of Electronic Communication Sciences, vol. 10, no. 3, 2015, pp. 349-356. https://doi.org/10.13067/JKIECS.2015.10.3.349
  7. S. Lee, C. Lee, J. Baek, D. Kim, and C. Kim "Characteristics of high frequency partial discharge for artificially defected extra high voltage accessories," 2000 Annual Report Conference on Electrical Insulation and Dielectric Phenomena, Victoria, BC, Canada, Canada, Oct. 2000.
  8. R. Cselko and I. Berta, "Challenges of partial discharge diagnostics of low-voltage cables," Journal of Electrostatics, vol. 71, no. 3, 2013, pp. 558-563. https://doi.org/10.1016/j.elstat.2012.12.042
  9. G. Toman, "Aging Management Program Guidance for Medium Voltage Cable Systems for Nuclear Power Plants," Technical report, Oct. 2009.
  10. Korea Electrical Safety Corporation, "A study on the counter plan and it's database construction customer's 22.9kV class power cable failures under PL system," Report, Feb. 2009.
  11. Hee-Chul Kim, "A Study on The Real-Time Data Collection/Analysis/Processing Intelligent IoT", Journal of the KIECS. pp. 317-322, vol. 14, no. 2, Apr. 30 2019, t. 94, pISSN 1975-8170
  12. Young-Man Kang, Hyi-Theak Ceong, and Seoung-Yeop Rhee, "CPW-Fed π-Shaped Antenna for Wideband", Journal of the KIECS. pp. 291-298, vol. 13, no. 2, Apr. 30 2018, t. 88, pISSN 1975-8170