Preventing cascading failure of electric power protection systems in nuclear power plant

  • Received : 2019.07.29
  • Accepted : 2020.06.07
  • Published : 2021.01.25

Abstract

Cascading failure is the main cause of large blackouts in electrical power systems; this paper analyzes a cascading failure in Hanbit nuclear power plant unit two (2) caused by a circuit breaker (CB) operation failure. This malfunction has been expanded to the loss of offsite power (LOOP). In this study, current practices are reviewed and then the methodologies of how to prevent cascading failures in protection power systems are introduced. An overview on the implementation of IEC61850 GOOSE messaging-based zone selective interlocking (ZSI) scheme as key solution is proposed. In consideration of ZSI blocking time, all influencing factors such as circuit breaker opening time, relay I/O response time and messages travelling time in the communication network should be taken into account. The purpose of this paper is to elaborate on the effect of cascading failure in NPP electrical power protection system and propose preventive actions for this failures. Finally, the expected advantages and challenges are elaborated.

Keywords

Acknowledgement

This research was supported by 2020 Research Fund of the KEPCO International Nuclear Graduate School (KINGS), Ulsan, Republic of Korea.

References

  1. A.G. Phadkel, J.S. Thorpz, Expose hidden failures to prevent cascading outages, IEEE Comput. Appl. Power 9 (1996) 20-23, https://doi.org/10.1109/67.526849.
  2. Y. Xiaohui, Z. Wuzhi, S. Xinli, W. Guoyang, L. Tao, S. Zhida, Review on power system cascading failure thoeries and studies, in: 2016 Int. Conf. Probabilistic Methods Appl. To Power Syst. PMAPS 2016 - Proc., Beijing, China, 2016, https://doi.org/10.1109/PMAPS.2016.7764167.
  3. P. Dehghanian, T. Popovic, M. Kezunovic, Circuit breaker operational health assessment via condition monitoring data, in: 2014 North Am. Power Symp, NAPS 2014, Washington, USA, 2014, https://doi.org/10.1109/NAPS.2014.6965427.
  4. C. koo Chang, Cascading failure in medium voltage network of NPP and counter measures, in: Proc. Korean Inst. Electr. Eng. Conf., Seoul, South Korea, 2018, pp. 1-3.
  5. H.H. Alhelou, M.E. Hamedani-Golshan, T.C. Njenda, P. Siano, A survey on power system blackout and cascading events: research motivations and challenges, Energies 12 (2019) 1-28, https://doi.org/10.3390/en12040682.
  6. IEEE Std 242-2001, IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems, Institute of Electrical and Electronics Engineers: Distributed in cooperation with Wiley-Interscience, NY, 2001.
  7. D. Ishchenko, A. Oudalov, J. Stoupis, Protection coordination in active distribution grids with IEC 61850, Proc. IEEE Power Eng. Soc. Transm. Distrib. Conf. (2012) 1-6, https://doi.org/10.1109/TDC.2012.6281478.
  8. C. Wester, M. Adamiak, J. Vico, IEC61850 protocol - practical applications in industrial facilities, in: Conf. Rec. - IAS Annu. Meet., Florida, USA, 2011, https://doi.org/10.1109/IAS.2011.6074474.
  9. K. Nimma, S. Faraj, Modeling intelligent control switch IEC 61850 based substation automation communication, Appl. Syst. Innov. 1 (2018) 7, https://doi.org/10.3390/asi1010007.
  10. T. Zhao, L. Sevov, Practical considerations of applying IEC61850 GOOSE based zone selective interlocking scheme in industrial applications, 66th Annu. Conf. Prot. Relay Eng. CPRE (2013) 263-270, https://doi.org/10.1109/CPRE.2013.6822042, 2013.
  11. C.S. Mardegan, R. Rifaat, Considerations in applying IEEE recommended practice for protection coordination in industrial and commercial power systems-Part i, in: IEEE/IAS 51st Ind. Commer. Power Syst. Tech. Conf. (I&CPS 2015), vol. 52, 2016, pp. 3705-3713, https://doi.org/10.1109/ICPS.2015.7266442.
  12. C. koo Chang, Mitigation of high energy arcing faults in nuclear power plant medium voltage switchgear, Nucl. Eng. Technol. 51 (2019) 317-324, https://doi.org/10.1016/j.net.2018.08.014.
  13. Y. Botza, M. Shaw, P. Allen, M. Staunton, R. Cox, M. Boughman, C. Roberts, W. Rominger, Configuration and performance of IEC 61850 for first-time users-UNC charlotte senior design project, in: 10th Annu. West. Power Deliv. Autom. Conf., 2008, pp. 1-11.
  14. M. Daboul, J. Orsagova, T. Bajanek, V. Wasserbauer, Testing protection relays based on IEC 61850 in substation automation systems, in: Proc. 16th Int. Sci. Conf. Electr. Power Eng. EPE 2015, 2015, pp. 335-340, https://doi.org/10.1109/EPE.2015.7161095.
  15. P. Jafary, A. Supponen, M. Salmenpera, S. Repo, Analyzing reliability of the communication for secure and highly available GOOSE-based logic selectivity, Secur. Commun. Network. (2019), https://doi.org/10.1155/2019/9682189, 2019.
  16. R. Carlos, I. Martinez, P. Goncalves, Resistance temperature sensor aging degradation identification using LCSR test, in: Int. Nucl. Atl. Conf. 2013, PE (Brazil), 2013, p. 10. https://inis.iaea.org/search/search.aspx?orig_q=RN:46021425.
  17. Acromag, Criteria for temperature sensor selection of T/C and RTD sensor types part 3 of 3. www.acromag.com, 2011. (Accessed 27 July 2019).
  18. A. Gedzurs, Temperature protection methods of induction motor, Res. Rural Dev. 1 (2015) 258-263.
  19. IEEE Std C37.119-2016, IEEE Guide for Breaker Failure Protection of Power Circuit Breakers, 2016.