Analysis of the Harmonic Resonance during Restoration of Primary Restorative Transmission System

시송전계통의 고조파 공진현상에 대한 분석

  • 이경섭 (광운대 공대 전기공학과) ;
  • 이흥재 (광운대 공대 전기공학과)
  • Published : 2006.05.01

Abstract

Power system restoration following a wide area or complete blackout starts with energizing primary restorative transmission systems. During this primary restoration process, unexpected over-voltage may happen due to nonlinear interaction between the unloaded transformer and the transmission system. This is known as the harmonic resonance phenomenon that may cause burning out of transformer or other devices. Since the harmonic resonance originates from the nonlinear characteristics, it is very difficult to predict the occurrence of this phenomenon. This paper reports the analyses of the harmonic resonance occurred in domestic power system. Various analyses and results of the harmonic over-voltage is presented based on the PSCAD/EMTDC simulations.

Keywords

References

  1. M. M. Adibi et al., 'Power System Restoration - A Task Force Report' IEEE Trans. on PWRS, Vol. 2, No. 2, pp. 271-277, May 1987
  2. M. M. Adibi et al., 'Power System Restoration Issues', IEEE Computer Applications in Power, Vol. 4, No. 2, pp. 19-24, April 1991 https://doi.org/10.1109/67.75871
  3. M. M. Adibi et al., 'Special Consideration in Power System Restoration The Second Working Group Report', IEEE Trans. on PWRS, Vol. 9, No. 1, pp. 15-21, Feb. 1994 https://doi.org/10.1109/59.317562
  4. G. Morin, 'Service Restoration Following a Major Failure on the Hydro-Quebec Power System', IEEE Trans. on PWRD, Vol. 2, No. 2, pp. 454-462, April 1987
  5. M. M. Adibi, et al., 'Overvoltage Control During Restoration(Power System Restoration Working Group Report)', IEEE Trans. on PWRS, Vol. 7, No. 4, pp. 1464-1470, Nov. 1992 https://doi.org/10.1109/59.207369
  6. 이홍재 외, '시송전 계통에서 자기여자 현상의 새로운 알고리즘 개발', 대한전기학회 논문지 54A권 3호, pp. 117-121, 2005
  7. 이홍재 외, 'EMTDC를 이용한 시송전계통의 고조파공진 분석', 대한전기학회 논문지 54A권 4호, pp. 172-176, 2005