Cooling Characteristics on the Forced Convection of an Array of Electronic Components in Channel Flow (II) - The Effect of the Reynolds Number (without the Heat Sink) -

채널 유동장 내에 배열된 전자부품의 강제대류 냉각특성에 관한 연구(II) -레이놀즈 수의 영향(히트싱크가 부착되지 않은 경우)-

  • Published : 2006.06.01

Abstract

Present study is concerned with an experimental study on the cooling characteristics of heat-generating components arranged in channels which are made by printed circuit boards. To estimate the thermal performance of the heat-generating components arranged by $5\times11$ in channel flow, three variables are used: the inlet velocity, the height of channel, and row number of the component. The cooling characteristics of the heat-generating components such as the surface temperature rise, the adiabatic temperature rise, the adiabatic heat transfer coefficient, and the effect of thermal wake are compared with the result of the experiment and the numerical analysis. The experimental result is in a good agreement with the numerical analysis. The heat transfer coefficient increases as the Reynolds number increases, while the thermal wake function calculated for each row decreases as the Reynolds number increases. In addition, it is found that Nu-Re correlation equation is Identical to the previous studies, and the empirical correlation equation between the thermal wake function and Re is presented.

Keywords

References

  1. Klinger, D. J., Nakada, Y. and Menendez, M. A., 1990, AT&T Reliability Handbook, Von Nostrand Reinhold, New York
  2. Lenmann, G. L. and Pembroke, J., 1991, Forced convection air cooling or simulated low profile electronic components: Part 1-base case, ASME Journal of Electronic Packing, Vol. 113, pp.21-26 https://doi.org/10.1115/1.2905361
  3. Moffat, R. J., Arvizu, D. E. and Ortega, A., 1985, Cooling electronic components: forced convection experiments with an air-cooled array, Proceedings of the 23rd National Heat Transfer, HTD-Vol. 48, pp.17-27
  4. Wirtz, R. A. and Mathur, A., 1994, Convection heat transfer distribution on the surface of an electronic package, ASME Journal of Electronic Packaging, Vol. 116, pp.49-54 https://doi.org/10.1115/1.2905493
  5. Nakayama, W. and Park, S. H., 1996, Conjugate heat transfer from a single surfacemounted block to forced convective air flow in a channel, ASME Journal of Heat Transfer, Vol. 118, pp.301-309 https://doi.org/10.1115/1.2825845
  6. Copeland, D., 1992, Effects of channel height and planar spacing on air cooling of electronic components, ASME Journal of Electronic Packaging, Vol. 114, pp.420-424 https://doi.org/10.1115/1.2905475
  7. Kim, K. S., Kim, W. T. and Lee, K. B., 1998, Cooling characteristics on the forced convection of an array of flat-form electronic components in channel flow, KSME International Journal, Vol. 12, No. 1, pp.132-142 https://doi.org/10.1007/BF02946541
  8. Kim, K. S. and Yang, J. S., 2006, Cooling characteristics on the forced convection of an array of electronic components in channel flow (I), Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 18, No. 1, pp. 73-80
  9. Kim, K. S., 1998, Cooling characteristics on the forced convection of an array of electronic components in channel flow, Ph. D. thesis, Pusan National University
  10. Moffat, R. J. and Anderson, A. M., 1990, Applying heat transfer coefficient data to electronics cooling, ASME Joumal of Heat Transfer, Vol. 112, pp. 882-890 https://doi.org/10.1115/1.2910495
  11. Kline, S. J. and McClintock, F. A., 1953, Describing uncertainties in vsingle-sample experiments, Mechanical Engineering, Vol. 75, pp. 3-8
  12. Wirtz, R. A. and, Dykshoorn, P., 1984, Heat transfer from arrays of flat packs in a channel flow, Proceeding of the Fourth-Annual International Electronics Packaging Society, Baltimore, pp.318-326